OPERATION
6
97
OPTIFLEX 1300 C
www.krohne.com
03/2014 - 4000172306 - HB OPTIFLEX 1300 R07 en
6.4.10 How to measure products with a low dielectric constant (ε
r
)
The device can measure the level of liquids and solids with low dielectric constants. The
minimum value depends on the probe type and the measuring mode.
Measuring mode limits
In direct mode, the device directly receives the reflection of the signal from the surface of the
tank contents.
TBF mode lets the device measure one product with low ε
r
. Unlike direct mode, the signal travels
through the liquid or solid to the end of the probe. It is reflected back to the electronics. The
liquid or solid must have a stable dielectric constant for accurate measurement.
How to prepare an installation for a device that measures in TBF mode
• If the probe end is not attached, the minimum distance between the probe end (of single cable
or rod probes) and the tank bottom must be 300 mm / 12¨. If the device has a coaxial, double
rod or cable probe, it is not necessary to have a minimum distance between the probe end and
the tank bottom.
• There must be no objects in a diameter of 600 mm / 24¨ around a single probe. There must be
no objects in a diameter of 200 mm / 8¨ around a double probe. It is not necessary to have an
empty space around a coaxial probe.
How to configure the device to measure in TBF mode
• Go to Supervisor > Advanced Setup > Installation Setup > Measuring Mode
Supervisor > Advanced Setup > Installation Setup > Measuring Mode
Supervisor > Advanced Setup > Installation Setup > Measuring Mode
Supervisor > Advanced Setup > Installation Setup > Measuring Mode.
• Select TBF from the menu. Push [^
^
^
^].
• To enter the exact value of the product's dielectric constant, go to Supervisor > Advanced
Supervisor > Advanced
Supervisor > Advanced
Supervisor > Advanced
Setup > Installation Setup > Product Er
Setup > Installation Setup > Product Er
Setup > Installation Setup > Product Er
Setup > Installation Setup > Product Er.
• Type in the exact value. Push [^
^
^
^].
Measuring mode
Probe type
Minimum dielectric constant
Direct
Coaxial
1.4
All other probes
1.6
TBF
All probes
1.1
CAUTION!
Do not change the product ε
r
value in Product ε
r
(menu item C.1.14) unless the new value is
known. If an incorrect value is used, the device will not measure accurately.
INFORMATION!
The device usually measures in Automatic
Automatic
Automatic
Automatic mode. If it cannot find a signal in Direct
Direct
Direct
Direct mode, the
device will switch automatically to TBF
TBF
TBF
TBF mode.