6

OPERATION

80

OPTIFLEX 1300 C

www.krohne.com

03/2014 - 4000172306 - HB OPTIFLEX 1300 R07 en

C. Advanced setup

Menu
No.

Function

Function description

Selection list

Default

C.1 Installation Setup

C.1.1

Installation

Type

The installation on the tank for the

device.

Socket, Stillwell, Nozzle

Nozzle

C.1.2

Tank Height

The distance from the tank connecting

flange face / thread stop down to the

tank bottom.

min-max:

0.165…60 m / 0.54…196.86 ft

3 m / 9.84 ft

C.1.4

Nozzle /

Stillwell Height

The height from the tank connecting

flange face / thread stop to the bottom

of the nozzle or...the height from the

tank connecting flange face / thread

stop to the bottom of the stillwell.

min-max:

0…60 m / 0…196.86 ft

100 mm /

3.94 in

C.1.5

Nozzle /

Stillwell

Diameter

The inner diameter of the nozzle or

stillwell.

min-max:

20…1000 mm / 0.79…39.37 in

100 mm /

3.94 in

C.1.6

Probe Length

Probe length is the distance from the

flange face / thread stop of the device

down to the bottom end of the probe

(including counterweight for cable

versions). If probe length has been

modified, enter the new value here. For

more data, refer to

How to decrease

the length of probes

on page 98.

min-max: blocking

distance…max. probe length

for that type (single/double

rod: 4 m / 13 ft, coaxial: 6 m /

20 ft, single cable: 35 m /

115 ft, double cable: 8 m / 26 ft)

Depends on the

probe type.

C.1.9

Blocking

Distance

The non-measuring range at the top of

the probe. It depends on the probe type

and the installation.

min-max:

0…(probe length) m /

0…(probe length) ft

Depends on the

probe type. For

more data,

refer to

Measurement

limits

on page

141.

Detection Delay This forces the device not to analyse

reflections in a defined zone

immediately below the flange. Increase

blocking distance to increase the

maximum value.

min-max:

0…(blocking distance) m /

0…(blocking distance) ft

Depends on the

"blocking

distance". See

C.1.9 (Blocking

Distance)

C.1.10

Reference

Offset

Offset relating to a reference location

(distance). This value is positive when

the reference location is above the

device flange face and negative if

below. For more data, refer to

Distance

measurement

on page 87.

min-max:

-tank height…50 m /

-tank height...164.05 ft

0 m / 0 ft

C.1.11

Tank Bottom

Offset

Offset relating to a reference location

(level). The device reference point for

this parameter is the bottom of the

tank (set in menu item C.1.2.0). This

value is positive when the reference

location is below the tank bottom and

negative if above. For more data, refer

to

Level measurement

on page 88.

min-max:

-tank height...3000 m /

-tank height...9843 ft

0 m / 0 ft

C.1.12

Time Constant

Increasing the time constant will

smoothen the integrated readings,

decreasing will roughen the readings.

min-max: 0 to 100 seconds

20 seconds for

solids

5 seconds for

liquids