Operation – KROHNE OPTIFLEX 1300C EN User Manual
Page 82
6
OPERATION
82
OPTIFLEX 1300 C
www.krohne.com
03/2014 - 4000172306 - HB OPTIFLEX 1300 R07 en
C.1.19.2
Conversion
Unit
The volume or mass unit used in the
conversion table. If "Free Unit" is
selected, the device uses the unit name
in menu item C.5.1.9.
m3, L, US gal, GB gal, ft3, bbl,
Tons, Kg, US Tons, GB Tons,
Free Unit
m3
C.1.20
Product
Density
A value greater than 0 that is used with
a volume conversion table to calculate
mass. This menu item is not available if
you have selected a mass unit.
0…20000 kg/m3
0
C.1.21
Volume / Mass
Table
The device uses this table to display
volume and mass readings. Give the
number of entries on the table. Push
[^
^
^
^]. Type in the height and the
corresponding volume / mass values.
For more data, refer to
How to
configure the device to measure
volume or mass
on page 89.
Number of entries min-max:
0…50
No table. Table
units are
selected in
menu items
C.1.19.1 and
C.1.19.2.
C.1.22
Linearisation
Table
The device uses this table to increase
on-site accuracy. Give the number of
entries plotted. Fill the tank. Make a
reference measurement and type in
the correct value next to the device
reading. For more data, refer to
Linearisation
on page 87.
Number of entries min-max:
0…50
No table
C.3 Output 1 (HART)
C.3.1
Output
Function
Select an output function to scale the
current values. This is not displayed in
the operator mode.
1 solid/liquid:
1 solid/liquid:
1 solid/liquid:
1 solid/liquid: Level, Distance,
Volume (Mass), Ullage Volume;
2+ liquids:
2+ liquids:
2+ liquids:
2+ liquids: Interface Level,
Interface Distance, Interface
Volume, Layer, Layer Volume
Level
C.3.2
4 mA Setting
This gives a measurement value to
4 mA (output 1).
minmax:
1
0 m / 0 ft
C.3.3
20 mA Setting
This gives a measurement value to
20 mA (output 1).
min.-max:
2
Depends on the
output function
C.3.4
Output Range
Sets the effective range of output 1
either with or without over-run
3.8…20.5 mA (NAMUR),
4…20 mA
4…20 mA
C.3.5
Error Handling
This sets the behaviour of current
output 1 if an error occurs. Hold
Hold
Hold
Hold means
that the output current stays at the
value where the error occurred. Hold
Hold
Hold
Hold is
not available if 3.8…20.5 mA (NAMUR)
is the output range.
3.6 mA, 22 mA, Hold
22 mA
Error Handling
Delay
The time after which the current output
changes to an error value. It shows
that there is a measurement error.
min-max: 0…900 sec (seconds) 60 sec
C.3.6
HART Address
Any HART
®
address greater than 0 will
activate HART
®
multidrop mode. The
current output stays constant at 4 mA.
min-max: 0…15
0
C.4 Output 2 (Passive)
C.4.1
Output
Function
Select an output function to scale the
current values (output 2). This is not
displayed in the operator mode.
1 solid/liquid:
1 solid/liquid:
1 solid/liquid:
1 solid/liquid: Level, Distance,
Volume (Mass), Ullage Volume;
2+ liquids:
2+ liquids:
2+ liquids:
2+ liquids: Interface Level,
Interface Distance, Interface
Volume, Layer, Layer Volume
Level
C.4.2
4 mA Setting
This gives a measurement value to
4 mA (output 2).
min-max:
1
0 m / 0 ft
Menu
No.
Function
Function description
Selection list
Default