6

OPERATION

82

OPTIFLEX 1300 C

www.krohne.com

03/2014 - 4000172306 - HB OPTIFLEX 1300 R07 en

C.1.19.2

Conversion

Unit

The volume or mass unit used in the

conversion table. If "Free Unit" is

selected, the device uses the unit name

in menu item C.5.1.9.

m3, L, US gal, GB gal, ft3, bbl,

Tons, Kg, US Tons, GB Tons,

Free Unit

m3

C.1.20

Product

Density

A value greater than 0 that is used with

a volume conversion table to calculate

mass. This menu item is not available if

you have selected a mass unit.

0…20000 kg/m3

0

C.1.21

Volume / Mass

Table

The device uses this table to display

volume and mass readings. Give the

number of entries on the table. Push

[^

^

^

^]. Type in the height and the

corresponding volume / mass values.

For more data, refer to

How to

configure the device to measure

volume or mass

on page 89.

Number of entries min-max:

0…50

No table. Table

units are

selected in

menu items

C.1.19.1 and

C.1.19.2.

C.1.22

Linearisation

Table

The device uses this table to increase

on-site accuracy. Give the number of

entries plotted. Fill the tank. Make a

reference measurement and type in

the correct value next to the device

reading. For more data, refer to

Linearisation

on page 87.

Number of entries min-max:

0…50

No table

C.3 Output 1 (HART)

C.3.1

Output

Function

Select an output function to scale the

current values. This is not displayed in

the operator mode.

1 solid/liquid:

1 solid/liquid:

1 solid/liquid:

1 solid/liquid: Level, Distance,

Volume (Mass), Ullage Volume;

2+ liquids:

2+ liquids:

2+ liquids:

2+ liquids: Interface Level,

Interface Distance, Interface

Volume, Layer, Layer Volume

Level

C.3.2

4 mA Setting

This gives a measurement value to

4 mA (output 1).

minmax:

1

0 m / 0 ft

C.3.3

20 mA Setting

This gives a measurement value to

20 mA (output 1).

min.-max:

2

Depends on the

output function

C.3.4

Output Range

Sets the effective range of output 1

either with or without over-run

3.8…20.5 mA (NAMUR),

4…20 mA

4…20 mA

C.3.5

Error Handling

This sets the behaviour of current

output 1 if an error occurs. Hold

Hold

Hold

Hold means

that the output current stays at the

value where the error occurred. Hold

Hold

Hold

Hold is

not available if 3.8…20.5 mA (NAMUR)

is the output range.

3.6 mA, 22 mA, Hold

22 mA

Error Handling

Delay

The time after which the current output

changes to an error value. It shows

that there is a measurement error.

min-max: 0…900 sec (seconds) 60 sec

C.3.6

HART Address

Any HART

®

address greater than 0 will

activate HART

®

multidrop mode. The

current output stays constant at 4 mA.

min-max: 0…15

0

C.4 Output 2 (Passive)

C.4.1

Output

Function

Select an output function to scale the

current values (output 2). This is not

displayed in the operator mode.

1 solid/liquid:

1 solid/liquid:

1 solid/liquid:

1 solid/liquid: Level, Distance,

Volume (Mass), Ullage Volume;

2+ liquids:

2+ liquids:

2+ liquids:

2+ liquids: Interface Level,

Interface Distance, Interface

Volume, Layer, Layer Volume

Level

C.4.2

4 mA Setting

This gives a measurement value to

4 mA (output 2).

min-max:

1

0 m / 0 ft

Menu
No.

Function

Function description

Selection list

Default