How to adjust the distance value to make the device measure level correctly

• Go to the signal screen in operator mode. For more data on how to get to the signal screen,

refer to

Operator mode

on page 65.

• Push [>>>>] one time to move the cursor right to select the level signal 1.
• Make a note of the distance value on the signal screen.
• Push [^

^

^

^] for three seconds.

i

The program mode screen is displayed.

• Move the cursor to Supervisor

Supervisor

Supervisor

Supervisor and push [^

^

^

^] 2.

i

Type in the supervisor password, if this is necessary. For more data, refer to

How to get

access to the supervisor mode

on page 68.

• Type in the distance value 3.

i

The selected signal is the level signal.

• Push [^

^

^

^] to accept your new value or push [>

>>>] and [

] (Esc) at the same time to reject it.

i

The display goes back to the signal screen.

How to adjust the interface distance value to make the device measure interface
correctly (devices for interface measurement only).

• Go to the signal screen in operator mode. For more data, refer to

Operator mode

on page 65.

• Push [>>>>] 2 times to move the cursor right to select the interface signal.
• Make a note of the distance value on the signal screen.
• Push [^

^

^

^] for three seconds.

i

The program mode screen is displayed.

Figure 6-7: Areas on the signal screen

1 Reference signal area (the value cannot be changed)
2 Level signal area (use the distance input function to change the level value)
3 Interface signal area (use the distance input function to change the interface value)
4 Probe end area (in TBF mode only – this value cannot be changed)

Figure 6-8: How to make the device follow the correct level signal