Operation – KROHNE OPTIFLEX 1300C EN User Manual
Page 91
OPERATION
6
91
OPTIFLEX 1300 C
www.krohne.com
03/2014 - 4000172306 - HB OPTIFLEX 1300 R07 en
How to adjust the distance value to make the device measure level correctly
• Go to the signal screen in operator mode. For more data on how to get to the signal screen,
refer to
Operator mode
on page 65.
• Push [>>>>] one time to move the cursor right to select the level signal 1.
• Make a note of the distance value on the signal screen.
• Push [^
^
^
^] for three seconds.
i
The program mode screen is displayed.
• Move the cursor to Supervisor
Supervisor
Supervisor
Supervisor and push [^
^
^
^] 2.
i
Type in the supervisor password, if this is necessary. For more data, refer to
How to get
access to the supervisor mode
on page 68.
• Type in the distance value 3.
i
The selected signal is the level signal.
• Push [^
^
^
^] to accept your new value or push [>
>>>] and [
] (Esc) at the same time to reject it.
i
The display goes back to the signal screen.
How to adjust the interface distance value to make the device measure interface
correctly (devices for interface measurement only).
• Go to the signal screen in operator mode. For more data, refer to
Operator mode
on page 65.
• Push [>>>>] 2 times to move the cursor right to select the interface signal.
• Make a note of the distance value on the signal screen.
• Push [^
^
^
^] for three seconds.
i
The program mode screen is displayed.
Figure 6-7: Areas on the signal screen
1 Reference signal area (the value cannot be changed)
2 Level signal area (use the distance input function to change the level value)
3 Interface signal area (use the distance input function to change the interface value)
4 Probe end area (in TBF mode only – this value cannot be changed)
Figure 6-8: How to make the device follow the correct level signal