beautypg.com

Installation – KROHNE OPTIFLEX 1300C EN User Manual

Page 31

background image

INSTALLATION

3

31

OPTIFLEX 1300 C

www.krohne.com

03/2014 - 4000172306 - HB OPTIFLEX 1300 R07 en

Installation on tanks containing one liquid and foam

• The bypass chamber must have a process connection that is above the maximum level of

liquid.

• The bypass chamber must have a process connection that is below the lowest measured level

of liquid.

Installation on tanks containing more than one liquid

• The bypass chamber must have a process connection that is above the maximum level of

liquid.

• The bypass chamber must have a process connection that is below the lowest measured level

of liquid.

• There must be more process connections along the length of the bypass chamber. These

must have a minimum diameter of 25 mm / 1¨ with a minimum distance of 100 mm / 4¨
between the holes.

• If the probe has a counterweight, make sure that there is enough space between the

counterweight and the wall of the stilling well.

• If the interface liquid does not have a layer of air above it, fit a vent at the top of the bypass

chamber. Refer to the illustration that follows:

Figure 3-21: Installation recommendations for bypass chambers with no air gap

1 Bypass chamber with no air gap
2 Air vent