Installation – KROHNE OPTIFLEX 1300C EN User Manual
Page 47
INSTALLATION
3
47
OPTIFLEX 1300 C
www.krohne.com
03/2014 - 4000172306 - HB OPTIFLEX 1300 R07 en
3.8.5 How to install a device with a threaded connection
Equipment needed:
• Device
• Gasket (not supplied)
• 50 mm / 2¨ wrench (not supplied)
• Make sure the tank connection is level.
• Make sure that you use the applicable gasket for the connection and the process.
• Align the gasket correctly.
• If the device is installed on a tank made of plastic or other non-conductive material, refer to
Recommendations for pits and tanks made of non-conductive materials
on page 49.
• Lower the probe carefully into the tank.
i
For more data on cable probes, refer to
How to install a cable probe in the tank
on page 48.
• Use 50 mm / 2¨ wrench to attach the process connection to the tank.
• Tighten the nut.
i
Refer to local rules and regulations for the correct torque to apply to the connection.
Figure 3-37: Threaded connection
INFORMATION!
If there is not sufficient clearance to install the device, remove the housing. Install the probe and
then put the housing back on the process connection. For more data, refer to How to turn or
remove the signal converter on page 53
.