Service – KROHNE OPTIFLEX 1300C EN User Manual

Page 122

background image

7

SERVICE

122

OPTIFLEX 1300 C

www.krohne.com

03/2014 - 4000172306 - HB OPTIFLEX 1300 R07 en

1 Attach the adaptor to the top of process connection.
2 Tighten the 4 socket head screws with a 4 mm Allen wrench.
3 Put the OPTIFLEX 1300 signal converter on the adaptor. Make sure that the adaptor fully en-

gages in the mating part (signal converter).

4 Tighten the socket set screw at the bottom of the signal converter with a 5 mm Allen wrench.

Procedure 3: How to attach the OPTIFLEX 1300 signal converter

Figure 7-9: Procedure 3: How to attach the OPTIFLEX 1300 signal converter

WARNING!
Be careful with the pin connector below the adaptor. If the pin connector is damaged, the device
will not measure level correctly.

INFORMATION!
The procedure that follows calibrates the new device. You must have 2 reference points (levels)
in the tank given by a different measurement solution (an approved level meter or indicator).
These points are identified as reference point 1 (R1) and reference point 2 (R2). R1 is the point
where the tank is approximately 20% full. R2 is the point where the tank is approximately 80%
full.