Interface measurement low

2

W

The product is lost in the

empty area. The

measurement is held at the

sensor length.

Fill the tank to at least the

bottom of the measuring

range to continue

measurement.

Layer measurement low

2

W

The layer is less than 50 mm /

2¨ thick.

Fill the tank with top product

until it is at least 50 mm / 2¨

thick.

Signal status

Reference pulse low

amplitude

W

Reference amplitude is less

than reference threshold 1.

This fault could occur

because of electrostatic

discharge in solid

applications.

Make sure that your

installation has ESD

protection. For more data,

refer to

Installation

on page

17.

Reference pulse lost

E

Reference amplitude is less

than reference threshold 2.

This fault could occur

because the device hardware

is defective.

Make sure that your

installation has ESD

protection. For more data,

refer to

Nozzles on conical

silos

on page 34.

Contact your supplier to

check that the electronics are

still functioning correctly.

Level pulse lost

W

This shows that the device

lost the level signal in direct

mode but finds the signal for

the end of the probe. It will

continue to measure level in

tank bottom following (TBF)

mode. This warning is only

displayed in automatic

measurement mode.

The device continues to

measure in TBF mode. If the

device does not measure

correctly, make sure the

amplitude of the level

threshold is correct. For

more data, refer to

Thresholds and parasitic

signals

on page 92.

Probe end pulse lost

W

The probe end pulse

amplitude is less than the

probe end threshold. This

means the device cannot find

the probe end to measure

level in TBF mode. The device

uses direct mode as an

alternative to TBF mode. This

error is only displayed in

automatic measurement

mode.

The dielectric constant of the

tank contents is too high.

Check that the Measurement

Measurement

Measurement

Measurement

Mode

Mode

Mode

Mode (menu item C.1.13) is

set to Direct

Direct

Direct

Direct or Automatic

Automatic

Automatic

Automatic.

Operating status

Overfill

W

1

The tank is full. The level or

the interface signal is lost in

the full area. The

measurement is held at the

blocking distance value.

This is also used for

applications with WHG

approval. Danger of overflow!

Remove the contents from

the tank until it is at a safe

level.

Error Message

Error

code

Description

Corrective action