OPERATION

6

83

OPTIFLEX 1300 C

www.krohne.com

03/2014 - 4000172306 - HB OPTIFLEX 1300 R07 en

C.4.3

20 mA Setting

This gives a measurement value to

20 mA (output 2).

min-max:

2

Depends on the

output function

C.4.4

Output Range

Sets the effective range of output 2

either with or without over-run

3.8…20.5 mA (NAMUR),

4…20 mA

4…20 mA

C.4.5

Error Handling

This sets the behaviour of current

output 2 if an error occurs. Hold

Hold

Hold

Hold means

that the output current stays at the

value where the error occurred. Hold

Hold

Hold

Hold is

not available if 3.8…20.5 mA (NAMUR)

is the output range.

3.6 mA, 22 mA, Hold

22 mA

Error Handling

Delay

The time after which the current output

changes to an error value. It shows

that there is a measurement error.

This value is set in the output 1 menu.

Read only

Refer to

function C.3.5

C.5 Device Setup

C.5.1

C.5.1

C.5.1

C.5.1

Display

Display

Display

Display

Settings

Settings

Settings

Settings

To display the information you need,

To display the information you need,

To display the information you need,

To display the information you need,

refer to these menu items.

refer to these menu items.

refer to these menu items.

refer to these menu items.

C.5.1.1

Language

Information can be displayed in any of

the 9 languages stored in the device. If

it is necessary to change the display

quickly to English, push [

] for 3

seconds in operator mode.

English, French, German,

Italian, Japanese, Chinese

(simplified), Portuguese,

Russian, Spanish

C.5.1.2

Display Mode

The display screen status will change

after the time given in C.5.1.3. (time

delay). Disable

Disable

Disable

Disable switches off this

functionality, Auto-Off

Auto-Off

Auto-Off

Auto-Off switches off the

display and Default Screen

Default Screen

Default Screen

Default Screen will show

the selected default screen. To set to

the default screen, push [

] for 1

second in the operator mode.

Disable, Auto-Off, Default

Screen.

Disable

C.5.1.3

Time Delay

The time after which the display will

switch to the status set in C.5.1.2

(Display Mode). You cannot select this

menu if C.5.1.2 (Display Mode) is set to

"Disable".

1, 3, 5, 10 minutes

1 minute

Contrast

The contrast control for the display

screen. You can select a shade of gray

between light gray (level 1) and black

(level 9).

Level 1, Level 2, Level 3, Level

4, Level 5, Level 6, Level 7,

Level 8, Level 9

Level 5

C.5.1.4

Length Unit

The length unit displayed in operator

mode.

m, cm, mm, inch, ft, ft-inch-

1/16inch, ft-inch-1/32inch,

Free Unit

m

C.5.1.5

Volume Unit

The volume unit displayed in operator

mode.

m3, L, US gal, GB gal, ft3, bbl

m3

C.5.1.6

Mass Unit

The mass unit displayed in operator

mode.

Tons, Kg, US Tons, GB Tons

Kg

C.5.1.7

Custom.

Length Unit

A non-standard length unit for the

conversion table. This is defined by the

supervisor.

FREE_UNIT

C.5.1.8

Custom.

Length Ratio

The conversion factor between the

length unit selected in C.5.1.4 (Length

Unit) and C.5.1.7 (Custom. Length

Unit). This ratio is a multiple of 1 mm.

min-max: 1…99999

1

C.5.1.9

Custom. Conv.

Unit

Non-standard conversion unit for the

conversion table. This is defined by the

supervisor.

FREE_UNIT

Menu
No.

Function

Function description

Selection list

Default