Operation – KROHNE OPTIFLEX 1300C EN User Manual
Page 83
OPERATION
6
83
OPTIFLEX 1300 C
www.krohne.com
03/2014 - 4000172306 - HB OPTIFLEX 1300 R07 en
C.4.3
20 mA Setting
This gives a measurement value to
20 mA (output 2).
min-max:
2
Depends on the
output function
C.4.4
Output Range
Sets the effective range of output 2
either with or without over-run
3.8…20.5 mA (NAMUR),
4…20 mA
4…20 mA
C.4.5
Error Handling
This sets the behaviour of current
output 2 if an error occurs. Hold
Hold
Hold
Hold means
that the output current stays at the
value where the error occurred. Hold
Hold
Hold
Hold is
not available if 3.8…20.5 mA (NAMUR)
is the output range.
3.6 mA, 22 mA, Hold
22 mA
Error Handling
Delay
The time after which the current output
changes to an error value. It shows
that there is a measurement error.
This value is set in the output 1 menu.
Read only
Refer to
function C.3.5
C.5 Device Setup
C.5.1
C.5.1
C.5.1
C.5.1
Display
Display
Display
Display
Settings
Settings
Settings
Settings
To display the information you need,
To display the information you need,
To display the information you need,
To display the information you need,
refer to these menu items.
refer to these menu items.
refer to these menu items.
refer to these menu items.
C.5.1.1
Language
Information can be displayed in any of
the 9 languages stored in the device. If
it is necessary to change the display
quickly to English, push [
] for 3
seconds in operator mode.
English, French, German,
Italian, Japanese, Chinese
(simplified), Portuguese,
Russian, Spanish
C.5.1.2
Display Mode
The display screen status will change
after the time given in C.5.1.3. (time
delay). Disable
Disable
Disable
Disable switches off this
functionality, Auto-Off
Auto-Off
Auto-Off
Auto-Off switches off the
display and Default Screen
Default Screen
Default Screen
Default Screen will show
the selected default screen. To set to
the default screen, push [
] for 1
second in the operator mode.
Disable, Auto-Off, Default
Screen.
Disable
C.5.1.3
Time Delay
The time after which the display will
switch to the status set in C.5.1.2
(Display Mode). You cannot select this
menu if C.5.1.2 (Display Mode) is set to
"Disable".
1, 3, 5, 10 minutes
1 minute
Contrast
The contrast control for the display
screen. You can select a shade of gray
between light gray (level 1) and black
(level 9).
Level 1, Level 2, Level 3, Level
4, Level 5, Level 6, Level 7,
Level 8, Level 9
Level 5
C.5.1.4
Length Unit
The length unit displayed in operator
mode.
m, cm, mm, inch, ft, ft-inch-
1/16inch, ft-inch-1/32inch,
Free Unit
m
C.5.1.5
Volume Unit
The volume unit displayed in operator
mode.
m3, L, US gal, GB gal, ft3, bbl
m3
C.5.1.6
Mass Unit
The mass unit displayed in operator
mode.
Tons, Kg, US Tons, GB Tons
Kg
C.5.1.7
Custom.
Length Unit
A non-standard length unit for the
conversion table. This is defined by the
supervisor.
FREE_UNIT
C.5.1.8
Custom.
Length Ratio
The conversion factor between the
length unit selected in C.5.1.4 (Length
Unit) and C.5.1.7 (Custom. Length
Unit). This ratio is a multiple of 1 mm.
min-max: 1…99999
1
C.5.1.9
Custom. Conv.
Unit
Non-standard conversion unit for the
conversion table. This is defined by the
supervisor.
FREE_UNIT
Menu
No.
Function
Function description
Selection list
Default