Technical data, 5 measurement limits – KROHNE OPTIFLEX 1300C EN User Manual

Page 141

background image

TECHNICAL DATA

8

141

OPTIFLEX 1300 C

www.krohne.com

03/2014 - 4000172306 - HB OPTIFLEX 1300 R07 en

8.5 Measurement limits

Measurement limits in mm and inches

80 is ε

r

of water; 2.3 is ε

r

of oil

Double cable and double rod probes

Figure 8-13: Measurement limits of the double cable probes (on the left side) and double rod probes (on the right side)

1 A1, Top dead zone:

A1, Top dead zone:

A1, Top dead zone:

A1, Top dead zone: Distance from the flange to the top limit of the measuring range. Refer to the notes and table that
follow.

2 A2, Bottom dead zone:

A2, Bottom dead zone:

A2, Bottom dead zone:

A2, Bottom dead zone: Length at the end of the probe, where measurement is not linear.

3 D, non measurement zone:

D, non measurement zone:

D, non measurement zone:

D, non measurement zone: Zone where measurement cannot be taken.

4 Product 1

Product 1

Product 1

Product 1

5 Gas (Air)

Gas (Air)

Gas (Air)

Gas (Air)

6 L, Probe length:

L, Probe length:

L, Probe length:

L, Probe length: Length specified by the customer in the order. This is also the maximum measuring length for some
probe types in direct mode and all devices that operate in TBF mode.

7 Tank Height

Tank Height

Tank Height

Tank Height

INFORMATION!
h

hh

h is the height of the nozzle. dddd is the diameter of the tank nozzle.

INFORMATION!

If h < d, then the top dead zone (A1) is equal to the top dead zone for the probe only. Refer to
the table that follows.

If h ≥ d, then the top dead zone (A1) is equal to the tank nozzle height plus the top dead zone
for the probe.

Probes

Top dead zone, A1

ε

r

= 80

Bottom dead

zone, A2

ε

r

= 80

Top dead zone, A1

ε

r

= 2.3

Bottom dead

zone, A2

ε

r

= 2.3

[mm]

[inches]

[mm]

[inches]

[mm]

[inches]

[mm]

[inches]

Double rod
Double cable

125

4.9

10

0.4

165

6.5

50

1.95