Technical data – KROHNE OPTIFLEX 1300C EN User Manual
Page 134

8
TECHNICAL DATA
134
OPTIFLEX 1300 C
www.krohne.com
03/2014 - 4000172306 - HB OPTIFLEX 1300 R07 en
Input and output
Current output
Current output
Current output
Current output
Output signal
(Output 1)
4…20 mA HART
®
or 3.8…20.5 mA acc. to NAMUR NE 43
6
Output signal
(Output 2 – optional)
4…20 mA (no HART
®
signal) or 3.8…20.5 mA acc. to NAMUR NE 43 (optional)
Resolution
±3 µA
Temperature drift
Typically 50 ppm/K
Error signal
High: 22 mA; Low: 3.6 mA acc. to NAMUR NE 43
Approvals and certification
CE
This device fulfils the statutory requirements of the EC directives. The
manufacturer certifies successful testing of the product by applying the CE mark.
Explosion protection
Explosion protection
Explosion protection
Explosion protection
ATEX
KEMA 04ATEX1218 X
II 1 G, 1/2 G, 2 G Ex ia IIC or Ex ia IIB or Ex ia IIA T6...T2;
II 1 D, 1/2 D, 2 D Ex iaD 20 or Ex iaD 20/21 or Ex iaD 21 IP6X T70°C...T95°C;
II 1/2 G, 2 G Ex d[ia] IIC or Ex d[ia] IIB or Ex d[ia] IIA T6...T2;
II 1/2 D, 2 D Ex tD[iaD] A21/20 or Ex tD[iaD] A21 IP6X T70°C...T95°C;
II 3 G Ex nA II T6…T2 X
IECEx
IECEx KEM 06.0024X
Ga Ex ia IIC T6…T2; Ex iaD 20 IP 6X T70°C…T95°C;
Ga/Gb Ex d[ia] IIC T6…T2; Ex tD[iaD] A21/20 IP 6X T70°C…T95°C
FM – Dual Seal-approved
NEC 500
NEC 500
NEC 500
NEC 500
XP-IS / Cl. I / Div. 1 / Gr. ABCD / T6-T1;
DIP / Cl. II, III / Div. 1 / Gr. EFG / T6-T1;
IS / Cl. I, II, III / Div. 1 / Gr. ABCDEFG / T6-T1;
NI / Cl. I / Div. 2 / Gr. ABCD / T6-T1
NEC 505
NEC 505
NEC 505
NEC 505
Cl. I / Zone 0 / AEx d[ia] / IIC / T6-T1;
Cl. I / Zone 0 / AEx ia / IIC / T6-T1;
Cl. I / Zone 2 / AEx nA[ia] / IIC / T6-T1
Hazardous (Classified) Locations, indoor/outdoor Type 4X and 6P, IP66, Dual Seal
CSA – Dual Seal-approved
CEC Section 18 (Zone ratings)
CEC Section 18 (Zone ratings)
CEC Section 18 (Zone ratings)
CEC Section 18 (Zone ratings)
Cl. I, Zone 1, Ex d, IIC (Probe: Zone 0) T6;
Cl. I, Zone 0, Ex ia, IIC T6;
Cl. I, Zone 2, Ex nA, IIC T6
CEC Section 18 and Annex J (Division ratings)
CEC Section 18 and Annex J (Division ratings)
CEC Section 18 and Annex J (Division ratings)
CEC Section 18 and Annex J (Division ratings)
XP-IS, Cl. I, Div. 2, Gr. ABCD; Cl. II, Div. 2, Gr. FG; Cl. III, Div. 2 T6;
IS, Cl. I, Div. 1, Gr. ABCD; Cl. II, Gr. FG; Cl. III T6
NEPSI
GYJ111195/96
Ex d ia IIC T2~T6 DIP A21/A20 T
A
T70°C~T95°C IP6X;
Ex ia IIC T2~T6 DIP A21/A20 T
A
T70°C~T95°C IP6X
DNV / INMETRO
DNV 12.0042 X
Ex ia IIC T6…T2; Ex ia IIIC T70°C...T95°C Da IP6X;
Ex d [ia Ga] IIC T6…T2 Ga/Gb; Ex tb [ia Da] IIIC T70°C...T95°C Db IP6X
KGS
11-GA4BO-0327X
11-GA4BO-0328X
Ex ia IIC T6~T2; Ex iaD 20 IP6X T70°C~T95°C;
Ex d[ia] IIC T6~T2; Ex tD[iaD] A21/20 IP6X T70°C~T95°C