TECHNICAL DATA

134

OPTIFLEX 1300 C

www.krohne.com

03/2014 - 4000172306 - HB OPTIFLEX 1300 R07 en

Input and output

Current output

Current output

Current output

Current output

Output signal

(Output 1)

4…20 mA HART

®

or 3.8…20.5 mA acc. to NAMUR NE 43

6

Output signal

(Output 2 – optional)

4…20 mA (no HART

®

signal) or 3.8…20.5 mA acc. to NAMUR NE 43 (optional)

Resolution

±3 µA

Temperature drift

Typically 50 ppm/K

Error signal

High: 22 mA; Low: 3.6 mA acc. to NAMUR NE 43

Approvals and certification

CE

This device fulfils the statutory requirements of the EC directives. The

manufacturer certifies successful testing of the product by applying the CE mark.

Explosion protection

Explosion protection

Explosion protection

Explosion protection

ATEX

KEMA 04ATEX1218 X

II 1 G, 1/2 G, 2 G Ex ia IIC or Ex ia IIB or Ex ia IIA T6...T2;

II 1 D, 1/2 D, 2 D Ex iaD 20 or Ex iaD 20/21 or Ex iaD 21 IP6X T70°C...T95°C;

II 1/2 G, 2 G Ex d[ia] IIC or Ex d[ia] IIB or Ex d[ia] IIA T6...T2;

II 1/2 D, 2 D Ex tD[iaD] A21/20 or Ex tD[iaD] A21 IP6X T70°C...T95°C;

II 3 G Ex nA II T6…T2 X

IECEx

IECEx KEM 06.0024X

Ga Ex ia IIC T6…T2; Ex iaD 20 IP 6X T70°C…T95°C;

Ga/Gb Ex d[ia] IIC T6…T2; Ex tD[iaD] A21/20 IP 6X T70°C…T95°C

FM – Dual Seal-approved

NEC 500

NEC 500

NEC 500

NEC 500

XP-IS / Cl. I / Div. 1 / Gr. ABCD / T6-T1;

DIP / Cl. II, III / Div. 1 / Gr. EFG / T6-T1;

IS / Cl. I, II, III / Div. 1 / Gr. ABCDEFG / T6-T1;

NI / Cl. I / Div. 2 / Gr. ABCD / T6-T1

NEC 505

NEC 505

NEC 505

NEC 505

Cl. I / Zone 0 / AEx d[ia] / IIC / T6-T1;

Cl. I / Zone 0 / AEx ia / IIC / T6-T1;

Cl. I / Zone 2 / AEx nA[ia] / IIC / T6-T1

Hazardous (Classified) Locations, indoor/outdoor Type 4X and 6P, IP66, Dual Seal

CSA – Dual Seal-approved

CEC Section 18 (Zone ratings)

CEC Section 18 (Zone ratings)

CEC Section 18 (Zone ratings)

CEC Section 18 (Zone ratings)

Cl. I, Zone 1, Ex d, IIC (Probe: Zone 0) T6;

Cl. I, Zone 0, Ex ia, IIC T6;

Cl. I, Zone 2, Ex nA, IIC T6

CEC Section 18 and Annex J (Division ratings)

CEC Section 18 and Annex J (Division ratings)

CEC Section 18 and Annex J (Division ratings)

CEC Section 18 and Annex J (Division ratings)

XP-IS, Cl. I, Div. 2, Gr. ABCD; Cl. II, Div. 2, Gr. FG; Cl. III, Div. 2 T6;

IS, Cl. I, Div. 1, Gr. ABCD; Cl. II, Gr. FG; Cl. III T6

NEPSI

GYJ111195/96

Ex d ia IIC T2~T6 DIP A21/A20 T

A

T70°C~T95°C IP6X;

Ex ia IIC T2~T6 DIP A21/A20 T

A

T70°C~T95°C IP6X

DNV / INMETRO

DNV 12.0042 X

Ex ia IIC T6…T2; Ex ia IIIC T70°C...T95°C Da IP6X;

Ex d [ia Ga] IIC T6…T2 Ga/Gb; Ex tb [ia Da] IIIC T70°C...T95°C Db IP6X

KGS

11-GA4BO-0327X

11-GA4BO-0328X

Ex ia IIC T6~T2; Ex iaD 20 IP6X T70°C~T95°C;

Ex d[ia] IIC T6~T2; Ex tD[iaD] A21/20 IP6X T70°C~T95°C