Operation – KROHNE OPTIFLEX 1300C EN User Manual
Page 79
OPERATION
6
79
OPTIFLEX 1300 C
www.krohne.com
03/2014 - 4000172306 - HB OPTIFLEX 1300 R07 en
B.2.6
Sensor Length
The distance from the flange
face/thread stop down to the bottom
end of the probe (excluding the
counterweight for cable versions). The
factory set value for probe length is
displayed. If probe length has been
modified, the new value is shown.
Read only (blocking
distance…60 m / 197 ft)
B.2.7
Probe Type
The mechanical design of the probe.
The factory installed probe type is
displayed.
Read only
B.2.8
Counterweight
Type
The mechanical design of a cable
probe's bottom end. The device will not
measure below the top of the
counterweight. The factory-installed
counterweight type is displayed.
Read only
Temperature
Temperature of the electronics block.
The display will automatically switch
off if the temperature is below -20°C /
-4°F or above +60°C / +140°F.
Read only
B.2.9
Calculated Er
Value
Dielectric constant [ε
r
] is a major
parameter for TDR level measurement
devices. This device is able to
automatically calculate and display
here the ε
r
of the top product.
Read only
B.2.10
Snapshot
Information
A summary of snapshot data used by
the device. Go to Snapshot
Snapshot
Snapshot
Snapshot setup menu
to update this data.
Read only
B.2.11
Application
Mode
This displays the description of the
algorithm applied to the measurement
function and application conditions.
This is configured in the Application
Application
Application
Application
setup menu.
Read only
B.2.12
Error Records
A log of device errors. Scroll down the
list and push [^
^
^
^] to display the error
details. Opening a log will remove the
error icon if it appeared in operator
mode.
Read only
B.2.14
Custom.
Length Unit
Non-standard length unit for the
conversion table. This is defined by the
supervisor. Go to Supervisor >
Supervisor >
Supervisor >
Supervisor >
Advanced Setup > Device Setup >
Advanced Setup > Device Setup >
Advanced Setup > Device Setup >
Advanced Setup > Device Setup >
Display Settings > Custom. Length Unit
Display Settings > Custom. Length Unit
Display Settings > Custom. Length Unit
Display Settings > Custom. Length Unit
or follow the procedure in the
Conversion
Conversion
Conversion
Conversion setup menu.
Read only
B.2.15
Custom. Conv.
Unit
Non-standard conversion unit for the
conversion table. This is defined by the
supervisor. Go to Supervisor >
Supervisor >
Supervisor >
Supervisor >
Advanced Setup > Device Setup >
Advanced Setup > Device Setup >
Advanced Setup > Device Setup >
Advanced Setup > Device Setup >
Display Settings > Custom. Conv. Unit
Display Settings > Custom. Conv. Unit
Display Settings > Custom. Conv. Unit
Display Settings > Custom. Conv. Unit
or follow the procedure in the
Conversion
Conversion
Conversion
Conversion setup menu.
Read only
Menu
No.
Function
Function description
Selection list
Default