beautypg.com

Micromod Micro-DCI: 53MC5000 Training Manual User Manual

Page 53

background image

Training Manual

Advanced Configuration Lab

6 - 3

Table 6.1.

Math Block
Function Codes

Function Code

Math Function

0 A

1 (K1*A)+K2

2 (K1*A)+(K2*B)+(K3*C)

3 (K1*A*B*C)+K2

4 (K1*(A/B))+(K2*C)

5 ((K1*A)+(K2*B)/C)+K3

6 ((K1*A*B)/C)+K2

7 ((A+K1)/B+K2))*K3

8 (K1*ABS(A))+K2

9 K1*(A*A((K2*B)+K3))

10 K1*(2*2((K2*A)+K3))

11 K1*LOG((K2*A)+K3)

20 Limiter

(K1

21 Limiter

((K1*C)


To sum 2 inputs we will use the Function Code 2. The formula is:


(A*K1) + (B*K2) + (C*K3)

where A, B and C are inputs and K1, K2 and K3 are coefficients. We will not connect
anything to input C and assign a value of 1 to coefficients K1 and K2. We will also
assign a value of 0 for K3 to disable the third input C.

1.

Configuration of the Math A module:

• Press the E-mode button (dot button) until you see DISPLAY/ CONFIGURE/

PROGRAM at the bottom of the display.

• Press the F2 button until

CONFIGURE

5

is displayed at the bottom.

• Press F3 to accept the configuration mode. On design level A controllers, the

bottom line should now display the following:

POINT

L

.

On a design

level B controller, the bottom line should read

DATAPOINT

5

or

MODULE

.

Press the F2 button until

DATAPOINT

5

is displayed.

• Press F3 to accept the DATAPOINT configuration mode. The bottom line should

now display the following:

POINT

L