Micromod Micro-DCI: 53MC5000 Training Manual User Manual
Page 36
Training Manual
Front Face Configuration Lab – Datapoint Configuration
4-4
Table 4-1
Commonly Used
Locations in Single
Loop Controller
Memory
Location
Value Parameter
B000
1
0
99
Function Index
Flexible Control
Suspended, All outputs frozen
Default database
B016
1
2
3
4
5
98
Link List Loader
CS1 PID Controller
CS2 Analog Back-up
CS3 Ratio Controller
CS4 Automatic / Manual
CS5 Ratio Auto / Manual
Default wirelist (ABB logo on front)
(Removes Control selection)
C256
ANI0 Span (engineering span)
C276
ANI0 Zero (engineering zero)
B269
Digital Filter (smoothing the constant)
L440
1
0
Square root (selects linear or sq. root)
Square root
Linear
C257
ANI1 Span (RSP, engineering span)
C277
ANI1 Zero (RSP, engineering zero)
B270
Digital Filter (smoothing time constant)
L441
1
0
Square root
Square root
Linear
A000
Con 0 Tag name (10 characters)
A001
Con 0 Engineering Units (7 characters)
C100
Process Variable (measured)
C120
Remote Setpoint (measured)
C103
Process Limit 1 (process alarm 1 setpoint)
C104
Process Limit 2 (process alarm 2 setpoint)
C105
Alarm Deadband (maintain alarm band)
C106
Proportional band (tuning parameter in percent)
C107
Reset time (tuning parameter in minutes)