Micromod Micro-DCI: 53MC5000 Training Manual User Manual

Page 36

background image

Training Manual

Front Face Configuration Lab – Datapoint Configuration

4-4

Table 4-1

Commonly Used
Locations in Single
Loop Controller

Memory
Location

Value Parameter

B000



1
0
99

Function Index
Flexible Control
Suspended, All outputs frozen
Default database

B016


1
2
3
4
5
98

Link List Loader
CS1 PID Controller
CS2 Analog Back-up
CS3 Ratio Controller
CS4 Automatic / Manual
CS5 Ratio Auto / Manual
Default wirelist (ABB logo on front)
(Removes Control selection)

C256

ANI0 Span (engineering span)

C276

ANI0 Zero (engineering zero)

B269

Digital Filter (smoothing the constant)

L440

1
0

Square root (selects linear or sq. root)
Square root
Linear

C257

ANI1 Span (RSP, engineering span)

C277

ANI1 Zero (RSP, engineering zero)

B270

Digital Filter (smoothing time constant)

L441

1
0

Square root
Square root
Linear

A000

Con 0 Tag name (10 characters)

A001

Con 0 Engineering Units (7 characters)

C100

Process Variable (measured)

C120

Remote Setpoint (measured)

C103

Process Limit 1 (process alarm 1 setpoint)

C104

Process Limit 2 (process alarm 2 setpoint)

C105

Alarm Deadband (maintain alarm band)

C106

Proportional band (tuning parameter in percent)

C107

Reset time (tuning parameter in minutes)

Table 4-1 Cont.

Memory Value

Parameter