Front Face Configuration Lab – Datapoint Configuration

4-6

Table 4- 2 Cont.

Alarm configuration
in Single Loop
Controller

Memory
Location

Value Parameter

C103

Process Limit 1

C104

Process Limit 2

C105

Alarm

Deadband

B335






0
1
2
3
4
5
6

Selection of Alarm Function
Hi/Low Alarms; C103 = High, C104 = Low
No Alarms
Hi Only; C103 = High
Low Only; C104 = Low
Hi/Hi-Hi; C103 = High, C104 = Hi-Hi
Low/Low-Low; C103 = Low, C104 = Low-Low
Deviation from Setpoint; C103 = positive
Deviation, C104 = negative Deviation

#

Alarm “Ticks” will appear on the standard control loop display. They are added to the
left of the process variable bargraph, refer to figure 4.2.

Figure 4-2.

Single loop display
with alarm ticks