4 technical specifications – Siemens S5-135U/155U User Manual
Page 510
10-14
System Manual
C79000-G8576-C199-06
10.4 Technical Specifications
Power supply
Supply voltage of the system bus
Power consumption
+ 5 V 5 %
450 mA max.
RESET input
Rated input voltage
Electrical isolation
Input voltage
for signal 0
for signal 1
Input current
Permissible cable length
24 V DC
Yes
–33 to + 5 V DC
or input open
+13 to + 33 V DC
8.5 mA
100 m max. unscreened
Sensor supply for RESET input
Rated output voltage
Electrical isolation
Output voltage
Output current
24 V DC
Yes
20 to 30 V DC
short-circuit proof to L–
20 mA max.
Relay contact
Loading of contact with resistive load
or inductive load
30 V DC/ 1 A max.
Safety test
Voltage test acc. to VDE 0160
Relay contacts referred to internal
RESET input referred to internal
RESET input referred to relay contacts
Surge voltage test acc. to IEC 255-4
Input referred to ground
500 r.m.s.
500 r.m.s.
500 r.m.s.
1kV; 1.2/50
ms
Interference test
Radio interference test acc. to IEC 255-4
Radio interference test acc. to IEC 65 (Co) 39
Input referred to ground: 1 kV; 1 MHz
Input referred to ground: 1 kV; burst
Mechanical data
Dimensions (w x h x d)
Weight
20 mm x 243 mm x 193 mm
270g
Monitoring Module