beautypg.com

Siemens S5-135U/155U User Manual

Page 114

background image

4-48

System Manual

C79000-G8576-C199-06

Requirement:
Redundant backup, “Spare power supply” with rechargeable battery. The
lithium battery in the rack in in full working order.

Step

Action

1

Disconnect the faulty power supply from the system voltage and remove it.

2

Set the jumpers on the spare power supply according to your needs.

3

Push the spare power supply into the rack and screw it in place.

4

Remove the right-hand fan subassembly from the spare power supply.

5

Connect up the replacement power supply.

6

Switch on the system voltage and the power supply in any order.

Reaction:
– The system runs up
– Both fans run at an increased speed
– The LEDs “Fan 3” and “RB low” light up.

7

Reinsert the right-hand fan subassembly.

8

After the system has run up, press the reset switch on the spare power
supply.

Reaction:
– The LED “Fan 3” goes out
– The fans run at their normal speed again
– The LED “RB low” shows the battery charge state.

Requirement:
No backup

Step

Action

1

Disconnect the faulty power supply from the system voltage and remove it.

2

Set the jumpers on the spare power supply according to your needs.

3

Push the spare power supply into the rack and screw it in place.

4

Connect up the spare power supply.

5

Switch on the system voltage and the power supply in any order.

Reaction:
– The system runs up.

Central Controllers and Expansion Units Power Supply Units