Siemens S5-135U/155U User Manual
Page 341
8-29
System Manual
C79000-G8576-C199-06
Terminals
Rated DC voltage of module
L+
Reference potential for DC voltage
L–
Rated AC voltage of module
L
Reference potential for AC voltage
N
Permissible line length for digital output modules
Allow for the line resistance and tolerance of the supply
voltage for the relevant output current.
Enable inputs
F+
F–
(Enable voltage according to the rated voltage of the mod-
ule)
Short-circuit signaling output (only when the short-
circuited output is at logic 1)
H+
(Supply for 1L+, referred to L- of the module)
Max. permissible supply voltage
for rated voltage 24 V DC (L+/L-)
1)
for rated voltage 60 V DC (L+/L-)
1)
for rated voltage 115 V/230 V AC (L/N)
36 V DC for 100 ms
90 V DC for 100 ms
276 V AC for 100 ms
Supply voltage ripple V
pp
referred to rated DC vol-
tage
15 %
max.
2)
Interference suppression at digital inputs
v 1.5 ms
3)
Interference pulse length at digital outputs
v 1.5 ms
3) 4)
Circuitry for inductive loads:
Protective devices to limit the breaking voltage are provided
on the digital output modules. Additional protective cir-
cuitry for the load is only required in exceptional cases.
Exception: 458 digital output module
Switching of capacitive loads:
50 nF max. at full load
Safety tests
Surge voltage test to IEC 255-4
DC: Input/output to L-: V
p
= 1 kV, 1.2/50 ms
AC: Input/output to L-: V
p
= 2.5 kV, 1.2/50 ms
RFI test to IEC 255-4
DC: Input/output to L-: V
p
= 1 kV, 1 MHz
AC: Input/output to L-: V
p
= 2.5 kV, 1 MHz
Safety test for the -4UA13/-4UA14 modules
Immunity from conducted interference on signal
line
1 kV to IEC 801-4 (burst) for -4UA13 module
2 kV to IEC 801-4 (burst) for -4UA14 module
Immunity from discharge of static electricity
8 kV discharge in air to IEC 801-2, equivalent to 4 kV con-
tact discharge (see Chap. 3 and page 4-16)
6 kV contact discharge for -4UA14 module
1)
Supply and signal voltages must be produced as functional voltage with safety separation.
2)
The supply voltage range values are limit values. They include ripple.
3)
If not otherwise specified
4)
Must be bridged by the signal receiver
Digital Input/Output Modules