10.3.3

Setting the Switch S5

ON: PESP‘ monitoring on

Monitoring time

RDY/ is suppressed in case of fault

RDY/ is also output in case of fault

ON:

OFF:

When BASP is active (“1” signal)

RDY/ is always output

125ms

500ms
250ms

1s

1

2

3

4

5

6

7

8

ON

OFF

Select the monitoring time (between 125 ms and 1 s) by switching one of the
switches S5/1 to S5/4 to ON. If none of the four switches S5/1 to S5/4 is in
the ON position, for safety reasons the monitoring time has been set to 1 s.
If serial interface modules and the link between IM 304 and IM 314 are used,
the PESP‘ monitoring is to be switched off (see Section 10.1.4: Control line
faults).

Should the acknowledgement signal (RDY/) not be suppressed in the event of
a fault, the switch S5/8 must be in the OFF position.

When a BASP signal is active, the RDY/ signal will always be output.

Monitoring Module