5 6es5 434-4ua12 digital input module – Siemens S5-135U/155U User Manual
Page 351
8-39
System Manual
C79000-G8576-C199-06
8.4.5
6ES5 434-4UA12 Digital Input Module
Rated input voltage (LH+)
DC 5 to 15 V
Rated input voltage (L+)
DC 12 to 24 V (NAMUR)
1)
Number of inputs
32
Isolation
Yes, 1 group of 32 inputs
Input voltage TTL:
for logic 0
for logic 1
CMOS:
for logic 0
for logic 1
0 to 0.8 V
2.4 to 5.0 V
0 V to 0.3 x LH+
0.7 V x LH+ to 1 x LH+
Rated input current
TTL:
for logic 0
for logic 1
CMOS:
for logic 0
for logic 1
NAMUR:
for logic 0
for logic 1
–1 mA
0.1 mA or open input
–1 to –3 mA (5 to 15 V)
0.1 to 0.3 mA (5 to 15 V)
v 1.2 mA
w 2.1 mA
Internal resistance
1 kilohm typical
Line resistance
50 ohms max.
Input frequency
100 Hz max.
Delay time
for positive-going edge
for negative-going edge
3 ms typical (1.4 to 5 ms)
3 ms typical (1.4 to 5 ms)
Coincidence factor (total load capability)
100 %
Permissible line length
TTL/CMOS
NAMUR
200 m max. unshielded
600 m max. unshielded
Power supply
Digital section from system bus
5 V, 80 mA typical
Supply voltage L+/L–
24 V (20 to 30 V)
Current consumption at L+/L–
100 mA each
Current consumption at LH+/LH–
150 mA each at 15 V input voltage
Current output from LH+/LH–
120 mA each at 8.5 V sensor supply (NAMUR)
2)
Power dissipation (rated operation)
5.5 W
Enable input (F+/F–)
Rated input voltage
5/ 15/ 24 V DC
Input voltage
for logic 0
for logic 1
–15 to 2 V
4 to 33 V
Rated input current
5 mA
Permissible line length
100 m max.
Voltage test to VDE 0160
Between group and ground point: 1250 V AC
Mechanical specifications
Dimensions (W x H x D)
20 mm x 255 mm x 195 mm
Weight
Approx. 0.45 kg
1)
NAMUR = Sensor with current output to DIN 19234, Standards Committee for Measurement and Control.
However, the module is not intrinsically safe.
2)
The current consumption from L+/L- increases accordingly.
Digital Input/Output Modules