Siemens S5-135U/155U User Manual
Page 412
9-30
System Manual
C79000-G8576-C199-06
Cycle time for 8 measured values with 2048 units
(max. delay time for measured-value acquisition)
Approx. 0.48 s at 50 Hz
Input resistance (with card) for input ranges:
$12.5 mV/$50 mV/$500 mV/Pt 100
$1 V
$5 V/$10 V
$5 V/$20 mA
4 to 20 mA
w 10 MW
90 k
W
50 k
W
25
W
31.25
W
Measuring point-related error signal
– for overflow
– for broken wire
Yes
Yes, configurable
(at
$12.5 mV, $ 50 mV $ 500 mV and Pt 100
1)
)
Max. permissible input voltage without destruction
$18 V; 75 V for 1 ms max. and duty ratio 1:20
Interference suppression for f = n x (50/60 Hz
$1 %)
– with common-mode interference
– with differential-mode interference
w 100 dB
w 40 dB, interference voltage amplitude
but 100 % max. of measuring range referred to peak value
Error referred to rated value
– linearity
– tolerance
at
w50 mV
at
$ 12.5 mV
– polarity reversal error
at
w 50 mV
at
$12.5 mV
– temperature error
$ 1 unit
$ 1 unit
$ 3 units
$ 1 unit
$ 2 units
1 x 10
–4
/K
Error caused by modules with input range
$ 1 V/$ 5 V /$ 10 V
$ 20 mA/4 to 20 mA
2 x 10
–3
; TC =
$ 10 x 10
–5
/K
10
–3
; TC =
$ 5 x 10
–5
/K
Voltage test to VDE 0160
Between inputs and ground point
tested at 500 V AC
Surge voltage test to IEC 255-4
Between inputs and L-:
V
p
= 1 kV, 1.2/50
µ
s
Extended Pt 100 measuring range
Measuring range including overrange
Resolution
Basic error at T = 25
o
C
Operational error at T = 0 to 65
o
C
Range card
Approx. - 100
o
C to + 100
o
C
0.025
o
C per unit
$0.2
o
C max.
$0.5
o
C max.
6ES5 498-1AA11
Environmental specifications
See technical specifications of the S5-135U/155U CC
1)
In the event of open-circuit of the live I
C+
and I
C-
lines, the digital value 0 is indicated.
Analog Input/Output Modules