beautypg.com

14 6es5 456-4ua12 digital output module – Siemens S5-135U/155U User Manual

Page 370

background image

8-58

System Manual

C79000-G8576-C199-06

8.4.14

6ES5 456-4UA12 Digital Output Module

Rated supply voltage L

115 to 230 V AC (47 to 63 Hz)

Number of outputs

16, conditional short-circuit protection

1)

Isolation

Yes, 2 groups of 8 outputs

Range for supply voltage

88 to 264 V AC

Fusing

6.3 A fast; 1 fuse per 4 outputs

Output voltage

for logic 1
for logic 0


L– 1.5 V min.
30 V max.

Residual current at logic 0

5 mA max.

Switching current (resistive, inductive load)

ventilated
not ventilated


40 mA to 2 A;

2)

6 A max. per 4 outputs

40 mA to 1 A;

2)

4 A max. per 4 outputs

Switching current for lamps

ventilated
not ventilated


40 mA to 2 A; 2.5 A max. per 4 outputs
40 mA to 1 A; 2.5 A max. per 4 outputs

Contactor size

per fuse group

for all outputs


0 (Type 3TB40) to 14 (Type 3TB58) at 230 V AC;
00 (Type 3TJ ..) to 10 (Type 3TB54) at 115 V AC;

0 (Type 3TB40) to 8 (Type 3TB52) at 230 V AC;
00 (Type 3TJ ..) to 4 (Type 3TB48) at 115 V AC;

Max. inrush current for

3 ms

20 ms

50 ms


25 A/group
15 A/group
13 A/group

Permissible line length

300 m max. unshielded

Power supply

Digital section from system bus

5 V, 100 mA typical

Power dissipation (rated operation)

39.0 W

Enable input (F+/F–)

Jumper in front connector

Voltage test to VDE 0160

Between two groups: 2000 V AC
Between group and ground point: 1500 V AC

Mechanical specifications

Dimensions (W x H x D)

40 mm x 255 mm x 195 mm

Weight

Approx. 0.7 kg

1)

Protected by a fuse

2)

Contactors of Series 3TJ can only be operated at 115 V AC.

Digital Input/Output Modules