14 6es5 456-4ua12 digital output module – Siemens S5-135U/155U User Manual
Page 370
8-58
System Manual
C79000-G8576-C199-06
8.4.14
6ES5 456-4UA12 Digital Output Module
Rated supply voltage L
115 to 230 V AC (47 to 63 Hz)
Number of outputs
16, conditional short-circuit protection
1)
Isolation
Yes, 2 groups of 8 outputs
Range for supply voltage
88 to 264 V AC
Fusing
6.3 A fast; 1 fuse per 4 outputs
Output voltage
for logic 1
for logic 0
L– 1.5 V min.
30 V max.
Residual current at logic 0
5 mA max.
Switching current (resistive, inductive load)
ventilated
not ventilated
40 mA to 2 A;
2)
6 A max. per 4 outputs
40 mA to 1 A;
2)
4 A max. per 4 outputs
Switching current for lamps
ventilated
not ventilated
40 mA to 2 A; 2.5 A max. per 4 outputs
40 mA to 1 A; 2.5 A max. per 4 outputs
Contactor size
per fuse group
for all outputs
0 (Type 3TB40) to 14 (Type 3TB58) at 230 V AC;
00 (Type 3TJ ..) to 10 (Type 3TB54) at 115 V AC;
0 (Type 3TB40) to 8 (Type 3TB52) at 230 V AC;
00 (Type 3TJ ..) to 4 (Type 3TB48) at 115 V AC;
Max. inrush current for
≤
3 ms
≤
20 ms
≤
50 ms
25 A/group
15 A/group
13 A/group
Permissible line length
300 m max. unshielded
Power supply
Digital section from system bus
5 V, 100 mA typical
Power dissipation (rated operation)
39.0 W
Enable input (F+/F–)
Jumper in front connector
Voltage test to VDE 0160
Between two groups: 2000 V AC
Between group and ground point: 1500 V AC
Mechanical specifications
Dimensions (W x H x D)
40 mm x 255 mm x 195 mm
Weight
Approx. 0.7 kg
1)
Protected by a fuse
2)
Contactors of Series 3TJ can only be operated at 115 V AC.
Digital Input/Output Modules