beautypg.com

Siemens S5-135U/155U User Manual

Page 148

background image

5-8

System Manual

C79000-G8576-C199-06

Given in the following overview are the functions of the RUN, STOP and
SYS FAULT status LEDs.

The STOP LED indicates a soft stop; the SYS FAULT LED indicates a hard
STOP.

The CPU 948 can process a user program (OB 39) cyclically at the soft
STOP, but the digital outputs remain inhibited. At the hard STOP, no program
can run and the CPU has “stopped.” This state can only be exited by
switching the system voltage off and on again.

RUN

LED

STOP

LED

SYS

FAULT

LED

Status

on

off

off

The CPU is in the RUN state (cyclic
operation).

on

on

on

Appears briefly after power-up of the unit.

off

off

off

CPU is in the initial start or program check
state.

off

on

off

CPU is in the soft STOP state.

off

rapid

flashing

off

CPU is in the soft STOP state.
Overall reset has been requested by switch or
from the operating system.

off

slow

flashing

off

CPU is in the soft STOP state. An error has
occurred; see the CPU 948 Programming
Guide for possible causes.

off

off

on

CPU is in the hard STOP state. No program
processing is taking place. You can only exit
from this state by switching the system
voltage off and on again.

Status Indicators

CPUs, Memory Cards, Memory Submodules, Interface Submodules