Siemens S5-135U/155U User Manual
Page 268
6-6
System Manual
C79000-G8576-C199-06
The individual actions are explained in more detail in the following.
Setting the number of occupied CPU slots on the coordinator:
923A Coordinator
Number of CPUs used
Jumper(s) at EP 62
2
7 - 10; 8 - 9
1)
3
7 -10
4
8 - 9
923C Coordinator
Coded by inserting only one DIL switch S1.4, S1.5 or S1.6 in the front
plate recess: (see Figure 6-2)
DIL S.
on
off
Effect
S1.1
S1.2
S1.3
S1.4
S1.5
S1.6
x
x
x
x
x
x
–
–
Enable test mode
No. of occupied CPU slots = 2
1)
No. of occupied CPU slots = 3
No. of occupied CPU slots = 4
1)
Setting when delivered
Setting the communication flag areas:
IF ...
THEN ...
you use
communication flag
areas on CPs (please
consult the relevant
manuals),
you must mask out these areas (blocks) on the
coordinator without fail, to avoid duplicated
addressing of the communication memory.
The 256 communication flag bytes can be masked
out in groups of 32. You do this by removing
jumpers at coding socket EP 7 on Coordinator A
(see Figure 6-1 for location) or EP 60 on
Coordinator C (see Figure 6-2).
Step 1
Step 2
Multiprocessor Operation/Coordinators