9 technical specifications – Siemens S5-135U/155U User Manual
Page 477
9-95
System Manual
C79000-G8576-C199-06
9.6.9
Technical Specifications
6ES5 466-3LA11 Analog Input Modules
Input ranges
0-20 mA; 4-20 mA;
"20 mA;
0-1.25 V; 0-2.5 V; 0-5 V;
1-5 V; 0-10 V;
"1.25 V; "2.5 V; "5 V;
"10 V
Number of inputs
16 single or 8 differential inputs in groups of
4 or 2 channels (selectable)
voltage or current measurement
Measuring principle
Instantaneous value encoding
Conversion time
25
ms typical (per channel)
Isolation
Yes
Permissible isolation between sensor ref. potential and
central ground point
25 V AC/60 V DC max.
Supply voltage
internal
external
+ 5 V +/- 5 %
None
Current consumption, internal
0.7 A typical
Encoding time per measured value
250
ms
Duration of cyclic sampling
(cycle time)
for 8 measured values
for 16 measured values
2 ms max.
4 ms max.
Input resistance
voltage measuring range
current measuring range
w 10 M W
125
W
Type of circuit for sensors
Two-wire circuit
Digital representation of the input signal
Selectable, following types of representation:
– 12-bit two’s complement
– 11-bit value with sign
– 12-bit binary
Max. permissible input voltage without destruction
$ 30 V max. (static) or
$ 75 V (pulse for 1 ms max. and duty ratio 1:20)
Interference voltage suppression common-mode interfer-
ence (Vpp = 1 V)
70 dB min.
Basic error limits
– voltage ranges except for 0-1.25 V;
$1.25 V
– current ranges and 0-1.25 V
;
$1.25 V
0.1 %
0.2 %
Analog Input/Output Modules