4-52
System Manual
C79000-G8576-C199-06
6ES5 955-3LF42
6ES5 955-3LC42
Output 1
Rated output voltage Vo/pN1
5.1 V DC
$ 1.2%
5.1 V DC
$ 1.2%
Rated output current Io/pN1
18 A
40 A
Basic load
0.5 A
1.6 A (typical)
3.1 A (worst case)
Ripple
v 1% of V
o/p1
v 1% of V
o/p1
Spikes
v 4% of V
o/p1
v 4% of V
o/p1
Static voltage tolerances
–
at 95% load variation
–
at 15% variation of V
i/p
–
at temperature variation / 1K
v 0.005% of V
o/p1
v 0.0005% of V
o/p1
v 0.02% of V
o/p1
v 0.08% of V
o/p1
v 0.0005% of V
o/p1
v 0.02% of V
o/p1
Dynamic voltage tolerances
at load surge 50% to 100% I
i/oN
–
overshoot
–
settling time
v 3% of V
o/p1
v 5 ms
v 3% of V
o/p1
v 5 ms
Maximum permitted capacity
100 mF
750 mF
Protection and monitoring
Voltage Monitor
Monitors voltage for
< 14 V and > 16 V
Monitors voltage for
< 14 V and > 16 V
Overvoltage shutdown V
o/p1
6V
$ 5%
6V
$ 5%
Undervoltage signal V
o/p1
4.75 V + 3%
4.75 V + 3%
Current limiting for overload
1.0 to 1.2 I
o/pN1
1.0 to 1.2 I
o/pN1
Test sockets for I
o/p1
On front plate (3 V
¢ 18 A)
linearity range:
0.5 V/2.8 A to 3 V/18 A
On front plate (3 V
¢ 40 A)
linearity range:
0.5 V/6.6 A bis 3 V/40 A
Signaling section
Signals for SIMATIC S5,
relays “Fan Warning, Fan Alarm,
Warning” 250V/3A
Signals for SIMATIC S5,
relays “Fan Warning, Fan Alarm,
Warning” 250V/3A
Green LED: “5V o.k.” for V
o/p1
LED lights up if
4.75 V < V
o/p1
LED lights up if
4.75 V < V
o/p1
Output 2
Rated output voltage V
o/pN2
DC 24 V (+ 25%, -12.5%)
DC 24 V (+ 25%, -12.5%)
Rated output current I
o/pN2
1 A
2.8 A
Total current X2 and front terminals
1 A max.
2.8 A max.
Ripple
v 1% of V
o/p2
v 1% of V
o/p2
Spikes
v 2% of V
o/p2
v 2% of V
o/p2
Protection and monitoring
Current limiting for overload
1 to 1.3 I
o/pN2
1 to 1.3 I
o/pN2
Green LED “24V o.k.” for V
o/p2
LED lights up if
V
o/p2
> 19.9 V to 21.1 V
LED lights up if
V
o/p2
> 19.9 V to 21.1 V
Maximum permitted capacity
0.2 mF
0.8 mF
Central Controllers and Expansion Units Power Supply Units