Siemens S5-135U/155U User Manual
Page 391
9-9
System Manual
C79000-G8576-C199-06
In the selective sampling mode, a measured value is encoded on the central
initiative of the CPU. At the start of conversion, the module must be
addressed once with a write operation (T PW) by the user program. An active
bit (T = 1) is set during encoding.
With the transition to T = 0, the measured value becomes valid. With
non-constant cycle times, there may be non-periodic measured value
aquisition. If you operate the module in this mode, you must set a module
address from 128 to 255. You can also use the address range from 0 to 127
for selective sampling after appropriate programming in DB 1 of the user
program.
Another method is that of time-controlled program processing. With this
method, certain program segments (e.g. FB 13) are automatically inserted
into program processing at the 100 ms rate by a time-
controlled block (OB 13). A constant timebase is thus achieved.
FB 13
SPRM-B
LEN=22
ABS
SHEET
1
SEGMENT 1
NAME: SELSAMPL
EXAMPLE OF SELECTIVE SAMPLING
0005
:
0006
:
0007
:L
PW128
READ ANALOG VALUE
0008
:T
MW128
IN TO AUX: FLAG FW 128
0009
:A
M 129.2
SCAN ACTIVITY =1?
000A
:JC
= END
IF = 1, JUMP TO END
000B
:T
FW10
IF = 0, MEASURED VALUE IN FW 10
000C
:T
PB128
INITIATE
SAMPLING
000D
END
:
(1ST VALUE INVALID AFTER START)
000E
000F
:
0010
:BE
You can read analog values of analog input modules with a function block
from the “basic functions” package.
The BASP signal is not interpreted by the 460 analog input module.
Selective Sampling
Time-Controlled
Program
Processing
Function Block
BASP (Output
Inhibit)
Analog Input/Output Modules