Siemens S5-135U/155U User Manual
Page 455
9-73
System Manual
C79000-G8576-C199-06
Measuring point-related error signal
– for overflow
– for broken wire
Yes
Yes, configurable
(at
$ 50 mV, $ 500 mV and Pt 100)
Max. permissible input voltage without destruction
$18 V; 75 V for 1 ms max. and duty ratio 1:20
Interference suppression for f = n x (50/60 Hz
$1 %)
– with common-mode interference
– with differential-mode interference
w 86 dB, but $1 V max.
w 40 dB, noise voltage amplitude
but 100 % max. of measuring range
referred to peak value
Error referred to rated value
– linearity
– tolerance
– polarity reversal error
– temperature error
$ 1 unit
$ 1 unit
$ 1 unit
1 x 10
–4
/K
Error caused by cards with input range
$ 1 V/$ 5 V /$ 10 V
$ 20 mA/4 to 20 mA
2 x 10
–3
; TC =
$ 10 x 10
–5
/K
10
–3
; TC =
$ 5 x 10
–5
/K
You select the desired mode of the analog input module by setting mode
switches I and II according to the following table.
Note that all the rockers of both mode switches marked with a dot must be
set, and some functions are defined by several rockers (e.g. 8- to 16-channel
operation, broken wire signal for 8 or 16 channels).
To activate the desired modes, press the rockers down on the side marked
with a dot.
Setting the Mode
Analog Input/Output Modules