9-18

System Manual

C79000-G8576-C199-06

Example:

(Special case) The temperature of the busbar of an electroplating bath is to be
measured with an uninsulated thermocouple.

+

U

E

+

U

CM

A

D

MUX

M+

M–

U CM

#

0 V Bus

Analog Input Module

Sensor,
Not Isolated

Range
Card for
4 Inputs

Figure 9-7

Measuring Circuit without Equipotential Bonding Conductor for the 460 Analog Input Module

The potential of the busbar with respect to the reference potential of the
module is, for example, 24 V DC. A 460 analog input module with isolated
input is used (U

CM

= 60 V AC/75 V DC). An equipotential bonding

conductor must not be laid here because it would short-circuit the busbar.

Analog Input/Output Modules