beautypg.com

Siemens S5-135U/155U User Manual

Page 446

background image

9-64

System Manual

C79000-G8576-C199-06

9.5.9

Connecting Resistance Thermometers to the 465 Analog Input
Module

The relevant resistance thermometer is fed with a current of 2.5 mA (I

C+

/I

C-

)

by a constant current generator via a 6ES5 498-1AA11 card. The voltage at
the Pt 100 is picked off at measurement inputs M+ and M-.

If only inputs 0 to 3 are assigned to resistance thermometers, you can connect
other current and voltage sensors to inputs 4 to 7 by means of a coding key. If
you use the Pt 100 for measurement, you cannot utilize channels 12 to 15.
Channels 8 to 11 supply the resistance thermometers which are connected at
inputs 0 to 3.

Note that the mode of the module is set to the 500 mV voltage range.

Analog Input/Output Modules