beautypg.com

Siemens S5-135U/155U User Manual

Page 422

background image

9-40

System Manual

C79000-G8576-C199-06

Press the individual rockers of the addressing switch downwards with a
ballpoint pen or similar object, but not a pencil.

On Setting

(Switch Pressed)

Addressing Switch

Address Bit

Decimal Significance of
the Address Bit

Adresse (dezimal)

ADB2 is not connected

ADB0 and ADB1 are not assigned

128

64

32

16

8

4

2

1

ADB7

ADB6

ADB5

ADB4

ADB3

ADB2

ADB1

ADB0

Free Field for Label with
Module Address and
marked Switch Settings

Figure 9-14

Labeling of the Addressing Switch

The address under which the module is referenced by the STEP 5 program is
independent of the slot.

For analog input and analog output modules (4 inputs) only the lowest
address (start address) is set. Other addresses (subaddresses) are decoded on
the module.

Note

The start address of the analog module must be a multiple of the double
channel number.
4 channels : 0, 8, 16, 24, ... 248

If one of the inputs or outputs (Channel 0 to 3) of a module is to be
addressed, the relevant subaddress must be specified in the program.

The subaddress of the input or output, based on the start address of the
module, is given by:

Start address + 2 x channel no. = subaddress

Start Address,
Subaddress

Analog Input/Output Modules