Siemens S5-135U/155U User Manual
Page 15

1-5
System Manual
C79000-G8576-C199-06
Additional measures are required when using the following modules.
A shielded signal cable is required for the following modules:
Order Number
Module
6ES5 432-4UA12
Digital input module 432
6ES5 453-4UA12
Digital output module 453-4
6ES5 457-4UA12
Digital output module 457-4
6ES5 482-4UA12
Digital I/O module 482-4 for IP 257
A filter (SIFI C B841213-C-B30 or equivalent) is required in the 230 V AC load voltage supply
for the following modules:
Order Number
Module
6ES5 436-4UA12
Digital input module 436-4
6ES5 436-4UB12
Digital input module 436-4
6ES5 456-4UA12
Digital output module 456-4
6ES5 456-4UB12
Digital output module 456-4
A filter (SIFI C, B841213-C-B30 or equivalent) is required in the 24 V DC load voltage supply
for the following modules:
Order Number
Module
6ES5 261-4UA11
Proportioning module IP 261
6ES5 432-4UA12
Digital input module 432
6ES5 453-4UA12
Digital output module 453-4
6ES5 457-4UA12
Digital output module 457-4
6ES5 465-4UA12
Analog input module 465-4
6ES5 470-4UB12
Analog output module 470-4
Notes on
Individual Modules