beautypg.com

Siemens S5-135U/155U User Manual

Page 396

background image

9-14

System Manual

C79000-G8576-C199-06

Remove an analog input/output module as follows:

Step

Action

1

Release the upper locking bar on the subrack and swivel it upwards and
out.

2

Slacken the screw in the upper part of the front connector. This causes the
front connector to be pressed out of the female connector of the module.
Contacts F+ and F- of the enable input at the upper end of the front con-
nector are thus opened first. If the enable input is active, power is removed
from the outputs and the module is isolated from the S5 bus.

3

Swing the front connector out and lift it away from the support pin of the
module.

4

Release the module by rotating the locking pin by 90

o

at the lower end of

the module. You can pull the module out of the subrack with a grip with
swivels outwards.

1

2

3

5

6

4

Module

Front
Connector

Support Mount

Support Pin

Figure 9-4

Module with Front Connector

1

Screw

2

Locking pin

3

Support mount

4

Support pin

5

Grip

6

Backplane connector

Comply with VDE Specifications 0110 and 0160 to carry out the wiring of
supply and signal lines which are to be connected to the programmable
controllers and front connectors of the modules.

Detailed information on cabinet assembly, cabinet ventilation and protective
measures can be found in Chapter 3.

Analog Input/Output Modules