1 installing and removing the interface submodules – Siemens S5-135U/155U User Manual
Page 233

5-93
System Manual
C79000-G8576-C199-06
5.11.1
Installing and Removing the Interface Submodules
To use an interface submodule, you must first install it in the CPU (outside
the central controller).
!
Caution
Switch off the power supply of the programmable controller before
removing the CPU.
Install your interface submodule in the following steps:
Step
Action
1
Check the jumper settings of your interface submodule:
PG submodule
See Section 5.11.2
V.24 submodule
See Section 5.11.3
TTY submodule
See Section 5.11.4
RS422 A/485 submodule
See Section 5.11.5
SINEC L1 submodule
See Section 5.11.6.
When the interface submodule is delivered, the jumpers are
already set so that you can usually fit it immediately.
2
Switch off the power supply of your PLC.
3
Remove the CPU.
4
Remove both screws on the submodule slot.
5
Remove the coverplate.
6
Insert the interface submodule through the front plate into the
plug-in connector (components in the same direction as the CPU).
7
Secure the submodule with the two screws (see step 4).
8
Insert the CPU in the central rack.
9
Switch on the power supply of your PLC again.
Installation
CPUs, Memory Cards, Memory Submodules, Interface Submodules