beautypg.com

Siemens S5-135U/155U User Manual

Page 43

background image

3-17

System Manual
C79000-G8576-C199-06

3.3.4

Special Measures for Interference-Free Operation

As a rule, inductances such as contactor or relay coils controlled by
SIMATIC S5 do not require external quenching elements in the circuit,
because the quenching elements are already integrated in the modules.

Inductances should only be fitted with quenching elements

S

when SIMATIC S5 output currents can be switched off by additionally
fitted contacts, such as relay contacts. In this case the integrated
quenching elements in the modules are no longer effective;

S

if they are not controlled by SIMATIC S5 modules.

You can place freewheel diodes, varistors or RC networks in circuit with
inductances.

Circuitry for DC-Operated
Inductances

With Diode

With Zener Diode

With Varistor

With RC Network

Circuitry for AC-Operated
Inductances

Figure 3-6

Quenching Circuits for Inductances

Fitting Quenching
Elements to
Inductances

Installation Guidelines