Siemens S5-135U/155U User Manual
Page 104
4-38
System Manual
C79000-G8576-C199-06
The following table contains several examples.
Requirement:
Enable EN present, jumper F - R closed
Causes
LED Indication
Relay
Reaction
Fans
Air filter/
air flow
Fan1 to Fan3
Alarm
Fan
Warning
Fan
Alarm
All fans in
order
In order
All LEDs dark
Dark
-
–
5 V, 15 V, 24 V present,
fans 1 to 3 running
One fan
failed
In order
Corresponding
LED lit
Dark
Active
–
5 V, 15 V, 24 V present,
faulty fan switched off, the other two
fans running at increased speed
Two fans
failed
In order
Corresponding
LEDs lit
Lit
Active
Active
Power supply switches off
All fans in
order
Dirty/halved
All LEDs
flashing
Lit
–
Active
Power supply switches off
Requirement:
Enable EN present, jumper F - R open
Causes
LED Indication
Relay
Reaction
Fans
Air filter/
air flow
Fan1 to Fan3
Alarm
Fan
Warning
Fan
Alarm
All fans in
order
In order
All LEDs dark
Dark
–
–
5 V, 15 V, 24 V present,
fans 1 to 3 running
One fan
failed
In order
Corresponding
LED lit
Dark
Active
–
5 V, 15 V, 24 V present,
faulty fan switched off, the other two
fans running at increased speed
Two fans
failed
In order
Corresponding
LEDs lit
Lit
Active
Active
5 V, 15 V, 24 V present,
faulty fans switched off, one fan
running at increased speed
All fans in
order
Dirty/halved
All LEDs
flashing
Lit
–
Active
5 V, 15 V, 24 V present,
fans 1 to 3 running
Note:
When the jumper “BB - AA” is closed the relay “Fan Alarm” is also
activated by the “output inhibit” signal (BASP via BASPA).
Fans and Fan
Monitoring
Central Controllers and Expansion Units Power Supply Units