Siemens S5-135U/155U User Manual
Page 457
9-75
System Manual
C79000-G8576-C199-06
Labeling of switches on the module cover:
II.
1)
resistance thermometer
16 channels ...mV/ ...mA
50 mV
without compensation
voltage/current
8 channels ...mV/ ...mA/ resist. therm.
500 mV/ ...mA/ resistance thermometer
with compensation
channel 4–7
I.
1)
*
*
8 channels
16 channels
channel 8–15
8channels
16channels
channel0–3
channel0–7
with
broken wire
detection
two’s complement
8 channels/resistance thermom.; mV/mA
line frequency 50 CPS
single scanning
channel 4–7
8 channels
16 channels
channel 8–15
8 channels
16 channels
channel 0–3
channel 0–7
with out
broken wire
detection
result and sign
16 channels mV; mA
line frequency 60 CPS
cyclics canning
resistance thermometer
consider instruction manual
voltage/current
1)
It is advisable to mark the selected switch setting in these fields.
On one 465 analog input module, you can insert four cards for the connection
of four inputs each, and secure them with a screw. There are voltage divider,
shunt and through-connection cards for the various ranges.
Circuit of the
cards 4x
Mode 50 mV
Mode
500 mV/ mA
Pt 100
-1AA11
-1AA21
-1AA31
-1AA41
-1AA51
-1AA61
-1AA71
M+
M–
M+
M–
M+
M–
M+
M–
M+
M–
M+
M–
M–
L+
L–
Range Card Type 6ES5 498–
M+
" 500 mV
Pt 100
"1 V
" 10 V
–
(
" 100 mV)
" 50 mV
" 5 V
4...20mA
2-wire trans.
" 20 mA
4...20mA
4-wire trans.
(
" 1 V)
(
" 2 mA)
(
" 500 mV)
–
For a defined mode (50 mV or 500 mV), you can insert cards with different
ranges for every four inputs, e.g. for the 500 mV mode:
S
4 inputs, range
$ 500 mV; 1 card 6ES5 498-1AA11
S
8 inputs, range
$ 20 mV; 2 cards 6ES5 498-1AA41
Unused inputs must be short-circuited (with Pt 100 operation, this also
applies to the unused current outputs).
Note that the bus interface of the module is activated with 24 V via enable
lines F+ and F- at the front connector.
Inserting Range
Cards
Analog Input/Output Modules