4.3.4

Maintenance and Repairs

The lithium battery should be replaced when a battery failure is indicated.
The backup times of the lithium battery are given in the following table:

I

backup

mA

0.25

1

2

3

4

5

New battery,
backup time in weeks

81.5

27.4

14.5

9.9

7.5

6.0

Battery 3 years old,
backup time in weeks

64.2

21.6

11.5

7.8

5.9

4.8

If a fan fails, replace it as quickly as possible. The behavior of the power
supply in the event of fan failure is described in Section 4.3.5.

The rechargeable battery should be replaced at regular intervals (service life
of 6 years at 40

o

C (104

o

F) ambient temperature). With a failed power

supply and failed battery, the backup times of the rechargeable battery are as
follows:

I

backup

mA

0.25

1

2

3

4

5

Backup time in weeks

18.8

6.3

3.4

2.3

1.7

1.4

The replacement intervals for the filter mat (with the air filter option) depend
on the ambient conditions under which the power supply unit is in operation.

Lithium Battery

Fans

Rechargeable
Battery

Filter Mat