beautypg.com

12 6es5 454-4ua13/4ua14 digital output module – Siemens S5-135U/155U User Manual

Page 366

background image

8-54

System Manual

C79000-G8576-C199-06

8.4.12

6ES5 454-4UA13/4UA14 Digital Output Module

–4UA13

–4UA14

Rated supply voltage L+

24 V DC

Number of outputs

16, short-circuit protected

1)

Isolation

Yes, 1 group of 16 outputs

Range for supply voltage

20 to 30 V DC

Fusing

6.3 A, slow

1 fuse per 4 outputs

7 A, fast

1 fuse per 4 outputs

Output voltage

for logic 1
for logic 0

L+ – 2 V min.

3 V max.

Switching current (resistive, inductive load)

10 mA to 2 A

2)

Residual current at logic 0

1 mA max.

Switching current for lamps

0.45 A max. (10 W)

Switching frequency

with resistive load
with inductive load

100 Hz max.

0.2 Hz max. at 1 A; 0.1 Hz at 2 A

Breaking voltage (inductive)

Limited to L+ – 47 V

Limited to L+ –55 V

Total switching current

4 A max. per 4 outputs

Coincidence factor (total load capability)

50 %

Permissible line length

400 m max., unshielded

Power supply

Digital section from system bus

5 V, 100 mA typical

Current consumption from L+/L–

24 V, 100 mA typical

24 V, 120 mA typical

Power dissipation (rated operation)

17.5 W

10 W

Enable input (F+/F–)

Rated input voltage

24 V DC

Input voltage

for logic 1
for logic 0

13 to 33 V

– 33 to 5 V

Rated input current

5 mA

Permissible line length

200 m max.

Short-circuit monitoring

Indicator for signaling output (H+)

Red LED for 4 outputs

Output voltage , referred to L–
(with feed at 1L+) for logic 1

for logic 0

1L+ – 5 V min.
3 V max.

1L+ –1,5 V min.

Switching current

10 mA max., limited

Voltage test to VDE 0160

Between group and ground point: 1250 V AC

Mechanical specifications

Dimensions (W x H x D)

40 mm x 255 mm x 195 mm

20 mm x 255 mm x 195 mm

Weight

Approx. 0.55 kg

1)

Short-circuit protection responds with line resistance

v 4,75 ohmd, irrelevant for the –4UA14.

2)

One digital input is permissible as minimum load.

Digital Input/Output Modules