3 technical specifications – Siemens S5-135U/155U User Manual
Page 192
5-52
System Manual
C79000-G8576-C199-06
5.4.3
Technical Specifications
Important for the USA and Canada
The following approvals have been obtained:
S
UL Listing Mark
Underwriters Laboratories (UL) to Standard UL 508, Report E 85972
S
CSA Certification Mark
Canadian Standard Association (CSA) to Standard C 22.2 No. 142,
Report LR 63533
Degree of protection
IP 00
Climatic ambient conditions
See Technical Specifications of the S5-135U/155U CC
Mechanical ambient conditions
See Technical Specifications of the S5-135U/155U CC
Noise immunity, electromagnetic
compatibility (EMC)
See Technical Specifications of the S5-135U/155U CC
Supply voltage
5 V
$ 5 %
24 V + 25 %/ -17 %
Current consumption at 5 V
5 A typical
Current consumption at 24 V
760 mA max.
Backup voltage
3.4 V
Backup current
20
mA typical (at 25 _C)
P area
O area
IM3 area
IM4 area
Total
Digital inputs with process image
Digital inputs without process image
or analog inputs
1024 max.
1024 max.
64 max.
–
2048 max.
128 max.
–
2048 max.
128 max.
–
2048 max.
128 max.
1024 max.
7168 max.
448 max.
Digital outputs with process image
Digital outputs without process image
or analog outputs
1024 max.
1024 max.
64 max.
–
2048 max.
128 max.
–
2048 max.
128 max.
–
2048 max.
128 max.
1024 max.
7168 max.
448 max.
Flags
2048
S flags
8192
Timers
256
Counters
256
Size of user memory
64 x 2
!) bytes max., EPROM or RAM
DB RAM
46 x 2
!) byte
Transmission rate of the serial PG interface
9600 bps
Program blocks PB
256
Sequence blocks SB
256
Function blocks FB
256
Function blocks FX
256
Data blocks DB
256, of which 253 are freely available
Data blocks DX
256, of which 253 are freely available
CPUs, Memory Cards, Memory Submodules, Interface Submodules