The modules must be inserted at the correct slots in the central controller.
The backup battery must be fitted and in order for the CPU to start.
Step
Action
Result
1
Set the mode switch to STOP.
2
Switch the system voltage on.
The following LEDs must light
up on the CPU:
–
Red STOP LED (flashing
rapidly)
–
Red BASP
2)
LED
3
Hold the MC
1)
switch in the
OVERALL RESET setting
and simultaneously set the
mode switch from STOP to
RUN.
The red STOP LED is now
permanently lit.
1)
MC: Momentary-contact
2)
BASP: Command output inhibit
Step
Action
Result
1
Set the mode switch to STOP.
2
Hold the MC switch in the
RESET setting and
simultaneously set the mode
switch from STOP to RUN.
–
Red STOP LED goes off
–
Green RUN LED lights up
–
Red BASP LED goes off
The CPU is now in the RUN state
but still has no user program.
You can also carry out a manual restart of the CPU 928B with the mode
switch. The CPU 928B Programming Guide will indicate when a manual
restart is permissible.
Step
Action
Result
3
Set the mode switch from
STOP to RUN.
–
Red STOP LED goes off
–
Green RUN LED lights up
–
Red BASP LED goes off
For maintenance purposes or in the event of a fault, this startup without user
program in single-processor operation can serve to establish whether the CPU
is operating without errors.
Startup
Overall Reset
Reset
Restart
CPUs, Memory Cards, Memory Submodules, Interface Submodules