beautypg.com

Siemens S5-135U/155U User Manual

Page 430

background image

9-48

System Manual

C79000-G8576-C199-06

When using the 4 to 20 mA inputs, you can select data representation of 0 to
1023 bits or 256 to 1279 bits by pressing the appropriate switch. You can
choose different data formats for all four input channels.

When the voltage or 0 to 20 mA inputs are used, the relevant switches remain
at the opposite settings.

Labeling of the switch on the module cover:

range 4...20 mA
0...1023

range 4...20 mA
256...1279
otherranges
0...1023

channel 2

channel 0

channel 1

channel 2

channel 3

channel 3

channel 1

channel 0

1)

1)

It is advisable to mark the selected switch setting in these fields.

Transducers are connected to the analog input module via shielded cables of
up to 200 m in length. When they are laid separately from power system
cables, distances of up to 500 m are possible.

An arbitrary mixture of voltage sensor, current sensor, two-wire and
four-wire transducers can be connected. For two-wire transducers, there are
four short-circuit protected supply terminals at the front connector.

!

Caution

To use two-wire transducers, the reference potential (common input) of these
channels must be connected to L-. This defeats the isolation between the
channels and the supply voltage L+/L-.

Note that the bus interface of the module is activated with 24 V via enable
lines F+ and F- at the front connector.

Setting the Data
Format for the 4 to
20 mA Range

Connecting
Transducers

Analog Input/Output Modules