beautypg.com

19 6es5 482-4ua11 digital input/output module – Siemens S5-135U/155U User Manual

Page 381

background image

8-69

System Manual
C79000-G8576-C199-06

8.4.19

6ES5 482-4UA11 Digital Input/Output Module

Rated supply voltage L+

24 V DC

Rated input voltage

24 V DC

Inputs

Number of inputs

16 min., 24 max.

Isolation

Yes, 1 group of 32 inputs/outputs

Input voltage

for logic 0
for logic 1


–33 to 5 V
13 to 33 V

Rated input current

8.5 mA typical

Delay time

0.3 ms typical

Input resistance

2.8 kilohms typical

Coincidence factor (total load capability)

100 %

Permissible line length

50 m max.

Supply voltage for 2-wire BERO

22 V to 33 V

Power supply

Digital section from system bus

5 V, 80 mA typical

Outputs

Number of outputs

8 min., 16 max., short-circuit protected

1)

Isolation

Yes

Fusing

6.3 A slow;
1 fuse per 8 outputs

Output voltage

for logic 1
for logic 0


L+ – 1.5 V min.
3 V max.

Switching current
(resistive, inductive load)


5 mA to 0.5 A

Switching frequency

with resistive load
with inductive load


120 Hz max.
2 Hz max. at 0.3 A; 0.5 Hz max. at 0.5 A

Breaking voltage (inductive)

Limited to L+ and – 27 V

Total switching current

4 A max. per 8 outputs

Coincidence factor (total load capability)

ventilated
not ventilated


100 %
50 %; 100 % up to 35

o

C

Permissible line length

400 m max.

Current consumption from L+/L–

24 V, 150 mA typical

Short-circuit monitoring

Indicator for signaling output (H+)

Red LED for every 8 outputs

Output voltage referred to L– (with feed at 1L+)

for logic 1
for logic 0

1L+ – 5 V min.
3 V max.

Switching current

10 mA max. current limiting

Enable input (F+/F–)

Jumper in front connector

Voltage test to VDE 0160

Between group and ground point: 1250 V AC

Mechanical specifications

Dimensions (W x H x D)

20 mm x 255 mm x 195 mm

Weight

Approx. 0.4 kg

1)

Short-circuit protection responds at line resistance

v 15 ohms

Digital Input/Output Modules