2 common technical specifications – Siemens S5-135U/155U User Manual
Page 385
9-3
System Manual
C79000-G8576-C199-06
9.2
Common Technical Specifications
Important for the USA and Canada
The following approvals have been issued:
S
UL Listing Mark
Underwriters Laboratories (UL) to Standard UL 508, Report E 85972 and
E116536 for the 466-7LA11 analog input module
S
CSA Certification Mark
Mark Canadian Standard Association (CSA) to Standard C 22.2 No. 142,
Report LR 63533C and LR 48323 for the 466-7LA11 analog input
module
Address range
128 to 255 (0 to 255)
Supply voltage L+
rated value
ripple V
pp
permissible range (including ripple)
reference potential
24 V
3.6 V
20 to 30 V
L–= M
ext
= 0 V
Voltage for the isolated enable inputs (only required when enable
jumper is inserted)
F+ = + 24 V
F– = 0 V
Line lengths for
Analog input modules with rated input range of
$ 12.5 m, $ 50 mV and Pt 100
50 m max. for shielded cables laid separately
from power system cables (see Chapter 3)
Analog input modules with rated input range of
$ 500 mV /
$ 1 / $ 5 / $ 10 V / $ 20 mA, 4 to 20 mA and Pt 100
200 m max., shielded
Analog output modules
200 m max., shielded
Temperature range
in operation
for storage ans transportation
0 to 55
o
C
– 40 to 70
o
C
Relative humidity
95 % max. at 25
o
C, no condensation
Site altitude
3500 m max. above sea level
Dimensions (W x H x D)
20 x 255 x 195 mm
Weight
Approx. 0.4 kg
Analog Input/Output Modules