2 installing a plc with distributed configuration – Siemens S5-135U/155U User Manual
Page 23
2-5
System Manual
C79000-G8576-C199-06
2.2.2
Installing a PLC with Distributed Configuration
To install a PLC in a distributed configuration, you have a choice of
parallel/symmetrical and serial communication. The following table shows
which interfaces and connecting cables can be used to connect the various
expansion units (EUs/ERs) to the CC in a distributed configuration.
Interface Module
in the CC
Expansion Unit
Interface Module in
the EU
Connecting Cable
Max. Permiss. Line Length
IM 301-3
6ES5 301-3AB13
(not for S5-155H)
IM 301-5
6ES5 301-5CA12
EU 183U
ER 701-2
ER 701-3
EU 183U
EU 185U
IM 310
1)
6ES5 310-3AB11
IM 310
1)
6ES5 310-3AB11
6ES5 721-0xxxx
1 m to 200 m
IM 304
6ES5 304-3UB11
ER 701-2
ER 701-3
EU 183U
EU 185U
IM 314
1)
6ES5 314-3UA11
6ES5 721-0xxxx
1 m to 600 m
IM 308
6ES5 308-3UA12
ER 701-2
ER 701-3
EU 183U
EU 185U
IM 318-3
6ES5 318-3UA11
6ES5 707-5AA00
V45551-F21-B5
up to 3000 m
ET 100U
(Catalog ST 52.1)
IM 318-8
6ES5 318-8MA12
ICM 560
–
IM 308-B
6ES5 308-3UB11
ET 200
IM 318-B
6ES5 318-8MB11
Cable connection
IM 307
6ES5 307-3UA11
ER 701-2
ER 701-3
IM 317
6ES5 317-3UA11
6ES5 722-2xxxx
Fiber optic cable up to 1500 m
EU 183U
EU 185U
IM 317
6ES5 317-3UA11
p
p
1)
The last IM 310 or IM 314 always requires a 6ES5 760-1AA11 terminator.
The ER 701-2 and ER 701-3 always additionally require an IM 306 for
communication via an IM 304, IM 307 or IM 308.
To install a PLC in a distributed configuration, you must observe the
following conditions:
S
With the IM 301/IM 310 pair of interface modules, you can only use I/O
modules (DI, DO, AI, AO) and IPs without page addressing in the EUs.
S
With the IM 304/314 pair of interface modules, you can use all IPs, CPs
and I/O modules in the EU 185U.
Note
The IM 307/317, IM 308/318 and IM 308-B/318-B each have their own
manual (see catalog).
Centralized and Distributed Configuration of a Programmable Controller