beautypg.com

10 6es5 451-4ua13/4ua14 digital output module – Siemens S5-135U/155U User Manual

Page 362

background image

8-50

System Manual

C79000-G8576-C199-06

8.4.10

6ES5 451-4UA13/4UA14 Digital Output Module

–4UA13

–4UA14

Rated supply voltage L+

24 V DC

Number of outputs

32, short-circuit protected

1)

Isolation

Yes, 1 group of 32 outputs

Range for supply voltage

20 to 30 V DC

Fusing

6.3 A slow
1 fuse per 8 outputs

7 A fast
1 fuse per 8 outputs

Output voltage

for logic 1
for logic 0


L+ – 1,5 V min.
3 V max.

Switching current
(resistive, inductive load)


5 mA to 0.5 A

Residual current at logic 0

0.5 mA max.

Switching current for lamps

0.22 A max. (5 W)

Switching frequency

with resistive load
with inductive load


100 Hz max.
2 Hz max. at 0.3 A; 0.5 Hz max. at 0.5 A

Breaking voltage (inductive)

Limited to L+ – 47 V

Limited to L+ –55 V

Total switching current

4 A max. per 8 outputs

Coincidence factor (total load capability)

ventilated
not ventilated


100 %
50 %; 100 % up to 35

o

C

Permissible line length

400 m max. unshielded

Power supply

Digital section from system bus

5 V, 80 mA typical

Current consumption from L+/L–

24 V, 150 mA typical

24 V, 200 mA typical

Power dissipation (rated operation)

17.0 W

6.4 W

Enable input (F+/F–),

Rated input voltage

24 V DC

Input voltage

for logic 1
for logic 0


13 to 33 V
– 33 to 5 V

Rated input current

5 mA

Permissible line length

200 m max.

Short-circuit monitoring

Indicator for signaling output (H+)

Red LED for every 8 outputs

Output voltage
referred to L– (with feed at 1L+)

for logic 1
for logic 0

1L+ – 5 V min.
3 V max.

1L+ –1,5 V min.
3 V max.

Switching current

10 mA max. limited

Voltage test to VDE 0160

Between group and ground point: 1250 V AC

Mechanical specifications

Dimensions (W x H x D)

20 mm x 255 mm x 195 mm

Weight

Approx. 0.45 kg

1)

Short-circuit protection responds with line resistance

v 15 ohms, irrelevant for the –4UA14 .

Digital Input/Output Modules