10 6es5 451-4ua13/4ua14 digital output module – Siemens S5-135U/155U User Manual
Page 362
8-50
System Manual
C79000-G8576-C199-06
8.4.10
6ES5 451-4UA13/4UA14 Digital Output Module
–4UA13
–4UA14
Rated supply voltage L+
24 V DC
Number of outputs
32, short-circuit protected
1)
Isolation
Yes, 1 group of 32 outputs
Range for supply voltage
20 to 30 V DC
Fusing
6.3 A slow
1 fuse per 8 outputs
7 A fast
1 fuse per 8 outputs
Output voltage
for logic 1
for logic 0
L+ – 1,5 V min.
3 V max.
Switching current
(resistive, inductive load)
5 mA to 0.5 A
Residual current at logic 0
0.5 mA max.
Switching current for lamps
0.22 A max. (5 W)
Switching frequency
with resistive load
with inductive load
100 Hz max.
2 Hz max. at 0.3 A; 0.5 Hz max. at 0.5 A
Breaking voltage (inductive)
Limited to L+ – 47 V
Limited to L+ –55 V
Total switching current
4 A max. per 8 outputs
Coincidence factor (total load capability)
ventilated
not ventilated
100 %
50 %; 100 % up to 35
o
C
Permissible line length
400 m max. unshielded
Power supply
Digital section from system bus
5 V, 80 mA typical
Current consumption from L+/L–
24 V, 150 mA typical
24 V, 200 mA typical
Power dissipation (rated operation)
17.0 W
6.4 W
Enable input (F+/F–),
Rated input voltage
24 V DC
Input voltage
for logic 1
for logic 0
13 to 33 V
– 33 to 5 V
Rated input current
5 mA
Permissible line length
200 m max.
Short-circuit monitoring
Indicator for signaling output (H+)
Red LED for every 8 outputs
Output voltage
referred to L– (with feed at 1L+)
for logic 1
for logic 0
1L+ – 5 V min.
3 V max.
1L+ –1,5 V min.
3 V max.
Switching current
10 mA max. limited
Voltage test to VDE 0160
Between group and ground point: 1250 V AC
Mechanical specifications
Dimensions (W x H x D)
20 mm x 255 mm x 195 mm
Weight
Approx. 0.45 kg
1)
Short-circuit protection responds with line resistance
v 15 ohms, irrelevant for the –4UA14 .
Digital Input/Output Modules