2 setting the power supply unit – Siemens S5-135U/155U User Manual

Page 126

background image

4-60

System Manual

C79000-G8576-C199-06

4.4.2

Setting the Power Supply Unit

The figure shows the jumper settings when the unit is delivered.

Connector

X1

Connector

X2

RR

Front Plate

LL

MM

NN

R

F

The jumper settings in bold print indicate the status when the unit is
delivered.

Function

Jumpers

Battery monitor (BAU) On

Battery monitor (BAU) Off

NN-MM closed

NN-MM open

PSU shutdown after fan fault

No PSU shutdown after fan fault (only LED
indication, relay signal)

F-R closed

F-R open

Battery fault will be indicated by fault state of the
signaling relay (contacts 2-3 closed).

Battery undervoltage (< 2.7V)

results in

battery fault signal (jumper

MM-NN).

Apart from “Batt. Low” LED

and output

of signal BAU, the signaling

relay can be

activated as of Version 6 of the

PSU

Battery fault will not be indicated by fault state of the
signaling relay

RR-LL closed

RR-LL open

Locations of
Jumpers

Functions of the
Jumpers

Central Controllers and Expansion Units Power Supply Units