Switch off the power supply before removing or inserting the module.
Proceed as follows to insert the CPU in the central controller:
Step
Action
1
Release the upper locking bar of the central controller and ensure
that the locking pin for the module is correctly positioned with the
slot-head horizontal.
2
Select the correct slot (based on the labelling of the locking bar).
Insert the CPUs in the S5-135U/155U from slot 11.
3
Push the module evenly into the guide rail until the lever over the
locking pin is horizontal.
4
Press the locking pin inwards on the bottom of the module and
rotate it 90
o
clockwise.
5
Secure the upper locking bar.
Note
If you install the CPU 928 -3UA21 as the replacement for a double-width
CPU, you must cover the slot which has been freed up with a blanking plate.
Proceed as follows to remove the CPU:
Step
Action
1
Release the upper locking bar of the central controller.
2
Release the locking pin of the module.
3
Press the release lever downwards and pull the module forwards
and out of the central controller.
Removing and
Inserting the
Module
Insertion
Removal
CPUs, Memory Cards, Memory Submodules, Interface Submodules