beautypg.com

Siemens S5-135U/155U User Manual

Page 178

background image

5-38

System Manual

C79000-G8576-C199-06

ADF LED

on

The user program has referenced an I/O address in the
process image under which no module is inserted.

ZYK LED

on

The maximum cycle monitoring time has been exceeded.

BASP LED

on

Command output is inhibited and the digital outputs will be
directly switched to the safe state.

A detailed description of interrupt and error handling can be found in the
CPU 928B -3UB21 Programming Guide.

LED SI1

LED SI2

Cause

on

on

No communication possible at both interfaces.
Internal error.

on

off

SI1:
No communication possible.
Internal error.

SI2:
If used, interface is initialized and ready.

off

on

SI1:
Interface is initialized and ready.

SI2:
No communication possible.
Wrong interface submodule inserted or wrong
parameters for interface or internal error.

off

off

First interface and, if used, second interface are
initialized and ready.

CPUs, Memory Cards, Memory Submodules, Interface Submodules