Timing chart (logic 107), Logic, Example: manual start input (x16) is used – IDEC FS1A Controller User Manual
Page 342

LOGIC
5-294
Timing chart (Logic 107)
Example: Manual start input (X16) is used.
Max. 0.1s
Safety input 1: X0
Safety output 1-1:
Y0
Monitor output for
safety input 1: Y4
Monitor output for Safety
output 1-1: Y12
Safety input 2:
X2, X3
Safety output 2-1:
Y2
Monitor output for Safety
output 2-1: Y17
Monitor output for Safety
output 2-2: Y20
Start input 1: X16
(Manual)
Monitor output for
safety input 4: Y7
Monitor output for Safety
output 1-2: Y13
State monitor output 3:
Y16
Max 6s.
Initialization
Safety input 1: X1
note 1)
Monitor output for
safety input 2: Y5
Safety input 4:
X6, X7
Safety output 1-2:
Y1
Safety output 2-2:
Y3
note 1)
Min. 0.1s
OFF delay time
OFF delay time
OFF delay time
OFF delay time
Safety
output
1, 2
ON
Power
ON
Safety
output
1, 2
ON
Safety
output
1
ON
Safety
output
2
ON
(Both safety input 3 and 5 are ON in this chart.)
Note 1) Input monitor error detection time is 0.5s.
About safety inputs that are not described in this chart, input monitor error detection time is as follows.
The time of dual channel direct opening input (X2 to X11) is 0.5s.
Refer to the following “Logic functions” for more details.